FAQ
60
Revision/New
305 General Requirements – Systems
Over 1000V ac/1500V dc
Leviton Comment: Article 305 is covered with Article
245 on page 57.
Revision/New
310.3(A)(B) Reconditioned Equipment
Leviton Comment: Article 310.3(A)(B) is covered with
Article 210.23(A) found on page 26.
Revision/New
312.10, 314.5 Screws Protruding into
Boxes – How Much is Allowable
Leviton Comment: We are covering Articles 312.10
and 314.5 together because they are very similar, and
both relate to screws protruding into boxes.
Change Summary
• The NEC has set limits on how far screws can protrude
into boxes.
Article 312 – Cabinets, Cutout Boxes, and Meter Socket
Enclosures
312.10 Screws or Other Fasteners. Screws or other
fasteners installed in the eld that enter wiring spaces shall
be as provided by or as specied by the manufacturer or
shall comply with the following as applicable:
(1) Screws shall be machine type with blunt ends.
(2) Other fasteners shall have blunt ends.
(3) Screws or other fasteners shall extend into the enclosure
no more than 6 mm (1⁄4 in.) unless the end is protected with
an approved means.
Exception to (3): Screws or other fasteners shall be permitted to extend into
the enclosure not more than 11 mm (7⁄16 in.) if located within 10 mm (3⁄8 in.)
of an enclosure wall.
Article 314 – Outlet, Device, Pull, and Junction Boxes;
Conduit Bodies; Fittings and Handhole Enclosures
314.5 Screws or Other Fasteners. Screws or other fasteners
installed in the eld that enter wiring spaces shall be as
provided by or specied by the manufacturer or shall
Material taken from the National Electric Code
®
is reprinted with permission
from NFPA 70
®
, 2023 edition. National Electrical Code
®
, Copyright 2022,
National Fire Protection Association, Quincy, MA. All rights reserved.