Submittal Sheet
THERMOSTATIC
MIXING VALVES
Submittal Data Sheet S-2008-LF
April, 2020
• Thermostatic Water Mixing Valve with 2.5
GPM (9.0 l/min) minimum flow capacity +
• 3/4” inlets, 3/4” outlet (19mm x 19mm)
sweat connections ONLY
• Integral combination check stops with wall
support
• 125 PSI (8.6 BAR) maximum operating
pressure
• Copper encapsulated thermostatic assembly
with stainless steel shuttle
• Temperature adjustment range, 90-140ºF
(32-60ºC) **
• Locking temperature regulating handle
• Internal parts of LF bronze, stainless steel
• Rough Bronze Finish
OPTIONS
____SUFFIX IT Inlet thermometers (shipped
loose)
____SUFFIX LWS Less wall support
____SUFFIX BDT Ball valve with dial
thermometer (shipped
loose)
NOTE: CP Chrome plated is NOT
AVAILABLE
*NOTE: A locking temperature regulator is simply a mechanical
setting to prevent unauthorized temperature set point changes.
AFTER INSTALLATION THE VALVE MUST BE RESET BY
THE INSTALLER !!
FLOW RATE
ECO-MIX
™
This product is certified to meet Low Lead
requirements of wetted surface area containing less
than 0.25% lead by weight
LV-981A-LF-______
2.5-43 GPM (9-163 l/min)
5 10 15 20 25 30 35 40 45 PSI
0.3 0.7 1 1.4 1.7 2.1 2.4 2.8 3.1 BAR
2.5 14 20 24 28 32 35 38 41 43 GPM
9 53 76 91 106 121 132 144 155 163 l/min
M IN. FLOW+
SYSTEM PRESSURE DROP
0
0
5(19)
10(38)
15(57)
20(76)
25(95)
30(114)
35(132)
5
(0.3)
10
(0.7)
15
(1.0)
20
(1.4)
25
(1.7)
30
(2.1)
35
(2,4)
40
(2.8)
45
(3.1)
50
(3.4)
GPM(l/min)
PRESSURE DROP
40 (151)
45 (170)
50 (189)
PSI (BAR)
SWEAT CONNECTIONS ONLY
+NOTE: The valve will maintain temperature with 0.5 GPM flow
from the domestic hot water loop when properly installed near the hot
water source with a continuously operating recirculation pump.
WARNING: This product can expose you to
chemicals including lead, which is known to the
State of California to cause cancer. For more
information, go to www.P65Warnings.Ca.gov
!
ASSE 1017 Certified
cUPC Certified