3 Technical data
General data and operating conditions
Conformity CE Low−Voltage Directive (2006/95/EC)
Approvals UL 508C Underwriter Laboratories (File−No. E132659)
Power Conversion Equipment
DC supply voltage
Voltage external +18 VDC −0 % ... +30 VDC +0 %
Current max. 8 A
(at max. load of all outputs)
Climatic conditions Class 3K3 to EN 50178
(without condensation, average relative humidity 85 %)
Temperature range
Transport −25 °C ...+70 °C
storage −25 °C ...+60 °C
Operation 0 °C ... +40 °C without power derating
+40 °C ... +55 °C with power derating
Power derating of output currents for t
a
> +40 °C: 2.5 %/K
Vibration resistance Resistant to acceleration up to 0.7 g
Permissible mounting
positions
in the Drive PLC on a plug−in−station for extension board
Insulation voltage to PE 50 V AC
Enclosure IP 20
Digital inputs X4
Level LOW (0 V ...+4 V)
HIGH (+13 V ...+30 V)
Input current 8 mA at 24 V
Digital outputs X3
Level LOW (0 V ...+4 V)
HIGH (+13 V ...+30 V)
Load capacity Output 05 ... 08: max. 1 A per output
Output 09, 010: max. 2 A per output
Dimensions
Height 145 mm (incl. terminal strips)
Width 72 mm
Depth 35 mm