Instruction Manual

Preliminary works
Coding by setting the DIP switches
EDK2174DB DE/EN/FR 3.0
10
H2WichtHinw-Codierung_DIP_en
Coding by setting the DIP switches
Remove the front plate of the CAN addressing module in order to set the baud rate and the
controller address in its interior with DIP switches.
Left DIP switch
(S1L, S2L, S3L, S4L, S5L)
Right DIP switch
(S1R, S2R, S3R, S4R, S5R)
2174CAN005
Setting the baud rate
Setthebaudratewiththeswitches S1L, S2Land S3L. Theswitchsettings requiredforsetting
the baud rate are represented in the following table:
Baud rate S1L S2L S3L
[kbaud]
500 OFF OFF OFF
250 ON OFF OFF
125 OFF ON OFF
50 ON ON OFF
1000 OFF OFF ON
Setting the controller address
The switches S4L and S5L as well as the switches S1R to S4R correspond to certain values:
S4L S5L S1R S2R S3R S4R S5R
Value 1 2 4 8 16 32 -
In order to set the controller address, add up the values in a way that their sum equals the
controller address. Then set those switches to ”ON” whose values you have added up.
Example:
Setting the controller address 27
Thesumofthevalueshastoequal27:1+2+8+16=27
Ö Switch setting:
S4L S5L S1R S2R S3R S4R S5R
ON ON OFF ON ON OFF -
Having set baud r ate and controller address, fasten the front plate to the CAN addressing
module.