User Manual
Data transfer
Process data signals of Lenze controllers
5
2111 INTERBUS fieldbus module
5.6
5.6.2
L
5.6-8
EDSIBS-1.0-06/2003
ThefollowingparameterscanbeassignedtothePO-data:
Index Subindex Name Explanation Lenze setting:
Index 6001
hex
see
6040 0 DRIVECOM control word PO data word 1 ^ 5.6-35
6042 0 DRIVECOM speed
setpoint
Speed setpoint [rpm] PO data word 2 ^ 5.6-41
6052 0 DRIVECOM percentage
setpoint
Speed setpoint [%]
100% = 16383
^ 5.6-42
5F78 0 Device control word
(L-C0135)
Table below
5CA7
1 AIF-IN.W1 AIF word 1. See the
following description.
)
))
) Note!
The assignment of the AIF-CTRL control word to PO data is only
useful, if the Drivecom status machine is switched off. This is
achieved by entering “ 0” under L-C1911.
Process data telegram to drive
Show/Hide Bookmarks