If necessary, supply the 2111 fieldbus module with a separate supply voltage
24 V DC via the two-pole plug connector ±10 % .
Plug connector Name Explanation
+ Vcc24 External supply 24 V DC ± 10 %, 150 mA
- GND24 Reference potential for external voltage supply
Use a separate power supply unit in each control cabinet.
Controller External voltage supply
820X Always required
821X / 822X / 824X and
93XX
Only necessary if the mains which supply the corresponding controllers is to be switched
off but the communication must not be interrupted.
8200 vector See information in “internal DC voltage supply”
Electrical connection Plug connector with threaded terminal end
Possible connections
rigid: 1.5 mm
2
(AWG 16)
flexible:
without wire crimp cap
1.5 mm
2
(AWG 16)
with wire crimp cap, without plastic sleeve
1.5 mm
2
(AWG 16)
with wire crimp cap, with plastic sleeve
1.5 mm
2
(AWG 16)
Tightening torque 0.5 ... 0.6 Nm (4.4 ... 5.3 lb-in)
Bare end 6mm
)
))
) Note!
Basic devices with extended AIF interface opening (8200 vector
front) can be internally supplied. The part of the drawing
highlighted in grey shows the jumper position.
l In the delivery state of the frequency inverter these are not
internally supplied.
l For internal voltage supply, put the jumper in the position
indicated below.
Lenze setting
only external voltage supply
Internal voltage supply
External DC voltage supply 6
Connection terminals 7
Internal DC voltage supply 8