Manual

EDS94AYCCA EN 5.0 - 06/2012 L 93
E94AYCCA communication manual (CANopen®)
Error messages
Possible causes and remedies
CAN module (MXI1): emergency configuration faulty [0x009f0000]
CAN module (MXI1): node guarding error 1 ... 32 [0x00a00000 ... 0x00a0001f]
CAN module (MXI1): NMT master configuration faulty [0x00a00020]
CAN module (MXI1) RPDO1: telegram not received or faulty [0x00a10000]
Response (Lenze setting printed in bold) Setting: not possible
None System fault Fault Trouble Quick stop by trouble : Warning locked Warning Information
Cause Remedy
CANopen communication module in MXI1: CAN
emergency configuration is faulty.
Faulty download of an »Engineer« or »PLC Designer«
project.
Invalid CAN settings according to DS301, V4.02
carried out in the »Engineer« or »PLC Designer«
project.
Repeat download
Correct CAN settings in the project and have project
regenerated.
Response (Lenze setting printed in bold) Setting: C13612/1...32 (; Adjustable response)
: None System fault ; Fault ; Trouble ; Quick stop by trouble ; Warning locked ; Warning ; Information
Cause Remedy
CANopen communication module in MXI1: cyclic node
monitoring
The CAN master has not received a response to a node
guarding telegram (RTR) by the node 1 ... 32 within
the time defined.
Reactivate CAN node by mains switching, restart of
the controller (C00002 = 11000) or "Reset node"
(C00002 = 92).
Parameterise node guarding monitoring time again
or switch off the monitoring.
Reset possibly active error status.
Tip: Before switching the mains and restarting the
controller, save the current parameter set (C00002 = 11).
Node guarding protocol
( 74)
Response (Lenze setting printed in bold) Setting: not possible
None System fault Fault Trouble Quick stop by trouble : Warning locked Warning Information
Cause Remedy
CANopen communication module in MXI1: on the CAN
master a configuration error has occurred in the network
management.
Faulty download of an »Engineer« or »PLC Designer«
project.
Invalid CAN settings according to DS301, V4.02
carried out in the »Engineer« or »PLC Designer«
project.
Node guarding or heartbeat parameterised
incorrectly.
Repeat download
Correct CAN settings in the project and have project
regenerated.
Response (Lenze setting printed in bold) Setting: C13591/1 / C14591/1 (; Adjustable response)
: None System fault ; Fault ; Trouble ; Quick stop by trouble ; Warning locked ; Warning ; Information
Cause Remedy
CANopen communication module in MXI1: CAN-IN1
error
PDO telegram length incorrect.
Error during transmission.
PDO time monitoring has been triggered.
Set correct telegram length for the CAN master
(transmitter).
Eliminate fault in the ambience (e. g. EMC).
Set different time monitoring or switch off time
monitoring.