Application
ÖLFLEX
CLASSIC 110 BLACK 0,6/1 kV cables are power and control cables with a black outer sheath for occasional flexi-
ble use and fixed installation subject to normal mechanical load conditions. They are among others designed for use in dry,
damp and wet rooms. Outdoor use: They may only be installed considering the indicated temperature range. At room tem-
perature they are widely resistant to acids, caustic solutions and certain oils. They are suitable for free non-continously re-
curring movement without tensile load or compulsory guidance. In addtion they are qualified for direct burial.
Application range:
Plant engineering and construction, industrial machinery, heating air conditioning systems, power station, stage application.
The cables are suitable for torsion application in wind turbines (WTG). The torsional load is limited to applications, as they
typically occur in the loop of a wind turbine.
Design
Design based on VDE 0250-1 and VDE 0276-627 bzw. HD 627 S1
Conductor fine wire strands of bare copper, acc. to IEC 60228 resp. VDE 0295, Class 5
Core insulation LAPP special PVC compound P8/1, better than the PVC compound TI2
in acc. with EN 50363-3 resp. VDE 0207-363-3
Core identification acc. to VDE 0293-1, with or without GN/YE ground conductor
black cores with white numbers
acc. to DIN EN 50334 resp. VDE 0293-334
Outer sheath PVC compound TM2 acc. to EN 50363-4-1 resp. VDE 0207-363-4-1
colour: Black, similar RAL 9005
Electrical properties at 20 °C
Nominal voltage U
0
/U 600 / 1000 V
Test voltage 4000 V AC
Mechanical and thermal properties
Min. bending radius occasional flexing: 15 x cable diameter
fixed installation: 4 x cable diameter
Temperature range occasional flexing: -5 °C up to +70 °C max. conductor temp.
fixed installation: -40 °C up to +80 °C max. conductor temp.
Torsion movement in WTG TW-0 (5000 cycles at ≥ +5°C)
TW-1 (2000 cycles at ≥ -20°C)
± 150 °/m at 1 revolution per minute
Flammability flame retardant in acc. with IEC 60332-1-2 resp. VDE 0482-332-1-2
Ozone resistance acc. to EN 50396