Data Sheet
U.I. Lapp
GmbH
DATA SHEET
ÖLFLEX
®
CLASSIC 100
DB 0010000
valid from: 11.02.2013
Originator: ROKR / PDC
Approved: HAPF / PDC
Dokument: DB0010000EN Page 1 of 1
All rights reserved acc. to DIN ISO 16016.
PD 0019/2.2_11.10EN
Application
ÖLFLEX
CLASSIC 100 cables are connecting- and control cables for occasional flexible use and fixed installation for medi-
um mechanical use. They are for use in dry, damp and wet rooms. They may only be installed outdoors with UV-protection
and in observation of the temperature range. At room temperature they are generally resistant against acids, caustics solu-
tions and certain oils. ÖLFLEX
CLASSIC 100 cables are used as supply and flexible connecting cable in machine tool manu-
facture, plant engineering, in power stations, in heating and air conditioning installations, etc. They are suitable for free non-
continuously recurring movement without tensile load or compulsory guidance.
This cable is suitable for torsion application in wind turbines (WTG). The torsional load is limited to applications, as they
typically occur in the loop of a wind turbine.
Design
Design based on EN 50525-2-51 resp. VDE 0285-525-2-51 / HD 21.13 S1 resp. VDE 0281-13
Conductor bare copper, fine wire strand in acc. with IEC 60228 resp. VDE 0295, Class 5
Core insulation PVC compound TI2 acc. to VDE 0207-363-3 with increased requirements
acc. to Lapp specification
Core identification with up to 5 cores are coloured-coded in acc. to HD 186 resp. VDE 0293
or HD308S2 that is VDE 0293-308; cables with more than 5 cores are colour-coded in
acc. to LAPP-ÖLFLEX colour-code.
Outer sheath PVC compound TM2 acc. to VDE 0207-363-4-1 with increased requirements
acc. to LAPP specification
Electrical properties
Nominal voltage 0,5 mm
2
to 1,5 mm
2
: 300 / 500 V
from 2,5 mm
2
: 450 / 750 V
from 2,5 mm
2
, fixed and protected installation: 600 / 1000 V
Test voltage 4000 V AC
Mechanical and thermal properties
Min. bending radius occasional flexing: 15 x cable diameter
fixed installation: 4 x cable diameter
Temperature range occasional flexing: -5 °C up to +70 °C max. conductor temp.
fixed installation: -40 °C up to +80 °C max. conductor temp.
Torsion movement in WTG TW-0 (5000 cycles at ≥ +5°C)
TW-1 (2000 cycles at ≥ -20°C)
± 150 °/m at 1 revolution per minute
Flammability flame retardant in acc. to IEC 60332-1-2 resp. VDE 0482-332-2-1
Tests acc. to IEC 60811 resp. VDE 0473-811, VDE 0472, EN 50395, EN 50396
EC-Directives This cable is conform to the EC-Directives 2006/95/EC (Low Voltage Directive) and
2011/65/EU (RoHS, Restriction of the use of certain hazardous substances).