Data Sheet

U.I. Lapp
GmbH
DATA SHEET
ÖLFLEX
®
CLASSIC 110 H
DB 10019900
valid from: 2013-11-08
Originator: KASC / PDC
approved: HESC / PDC
Document: DB10019900EN
All rights reserved acc. to DIN ISO 16016.
PD 0019/2.2_11.10EN
Application
ÖLFLEX
®
CLASSIC 110 H cables are halogen-free, oil resistant, highly flame retardant, power and control cables designed
for the European and North American market, for occasional flexible use and fixed installation under normal mechanical load
conditions. They are among others for use in dry, damp and wet rooms. Considering the temperature range, a temporary
outdoor use is possible. Continuous busy movements, compulsory guidance respectively usage on cable drums or pulleys or
under a strain of more than 15 N / mm² is not allowed. ÖLFLEX
®
CLASSIC 110 H cables are particularly used in areas,
where human and animal life as well as valuable property are exposed to high risk of fire hazards. In the event of a fire mini-
mal toxic and no corrosive gases occur.
Application range:
public buildings; airport, railway station; plant engineering, industrial machinery; heating and air conditioning systems, stage
applications
USE according to UL: FRPE sheathed cable for internal wiring of appliances and external interconnection or internal
wiring of electronic equipment
Design
Design acc. to UL AWM 758, Style 21089 and
based on EN 50525-3-11 resp. VDE 0285-525-3-11
Approval UL AWM 758, Style 21089 (File No. 63634)
Conductor fine wire strands of bare copper, acc. to IEC 60228 resp. VDE 0295, Class 5
Core insulation halogen free compound TI6, polyolefin based,
acc. to EN 50363-7 resp. VDE 0207-363-7, with increased requirements
Core identification acc. to VDE 0293-1, with or without GN/YE ground conductor
black cores with white numbers acc. to DIN EN 50334 resp. VDE 0293-334
Outer sheath halogen free compound HM2, polyolefin based, acc. to DIN VDE 0250-214,
with increased requirements,
LAPP special compound LP Ultraflex FR
colour: silver grey, similar RAL 7001
Electrical properties
Nominal voltage VDE U
0
/ U: 300 / 500 V
UL: 600 V
Test voltage core / core 4000 V AC
Mechanical and thermal properties
Min. bending radius occasional flexing: 10 x outer diameter
fixed installation: 4 x outer diameter
Temperature range occasional flexing (VDE): -30 °C up to +70 °C max. conductor temp.
occasional flexing (UL): -30 °C up to +75 °C max. conductor temp.
fixed installation (VDE): -40 °C up to +80 °C max. conductor temp.
fixed installation (UL): -40 °C up to +75 °C max. conductor temp.