Data Sheet

DATA SHEET
0034302
UNITRONIC
®
LiYCY
valid from :
04.09.2006
elaborated by:
TE-K: : M. Herb
Document: DB0034302_2EN page 1 of 1
Nr.: 0019/0894
Application
UNITRONIC
LiYCY is a flexible, screened cable for fixed installation and flexible use, but not for high flexible
applications in power chains and permanently moved machines. The screen is a protection against electrical
interference.
UNITRONIC
LiYCY cables are for use in dry, damp and wet rooms, but not outside.
Design and electrical characteristics acc. to VDE 0812.
Design
Conductor fine-wire strands of bare copper wire; 0.14 mm² to 1.5 mm² , 7-wired for 0.34 m
Insulation PVC compound YI2 in acc. with VDE 0207 part 4
Coding to DIN 47100
Stranding cores twisted in layers, wrapping by plastic foil
Screening braid of tinned copper, coverage approx. 85 %
Sheath PVC compound TM2 in acc. to VDE 0207 part 5, grey
Marking on the sheath
LAPPKABEL UNITRONIC
®
LiYCY Part No. . . . .
Technical Data
Loop resistance 0.14 mm²
max. /km
148
0.25 mm²
max. /km
79.9
0.34 mm²
max. /km
57.5
0.5 mm²
max. /km
38.9
0.75 mm²
max. /km
26
1.0 mm²
max. /km
19.5
1.5 mm²
max. /km
13.3
Specific insulation resistance
min. Gxcm
10
Mutual capacitance core/core nF/km
ca. 120
core/screen nF/km
ca. 160
Inductivity mH/km
ca. 0.65
Operating Voltage (not for power purposes) V
250
Test voltage U
eff.
V
1200
Temperature range static °C
- 40 to + 80
Minimum bending radius static
6 x Ø cable
moved
15 x Ø cable
Flame propagation flame retardant to VDE 0482, part 265-2-1 / IEC 60332-1