Data Sheet
U.I. Lapp
GmbH
DAT
A SHEET
ÖLFLEX
®
550 P
DB 0013600
valid from: 2013-02-01
Originator: KASC / PDC
approved: HAPF / PDC
Document: DB0013600EN Page 1 of 1
All rights reserved acc. to DIN ISO 16016.
PD 0019/2.2_11.10EN
Application
ÖLFLEX
®
550 P cables are high flexible oil-resistant power cables with an isolation of a compound of rubber and an outer
sheath of Polyurethane for flexible use and fixed installation for increased mechanical abuse. They are for use in dry, damp
and wet rooms. Under following to the indicate temperature range is a use outside possible. Continuous, busy movements,
usage of these cables in moving cable carriers, respectively on motor drum guidance or under a strain of more than 15
N/mm² is not allowed. ÖLFLEX
®
550 P cables are increased oil resistant and at room temperature generally resistant
against acids and caustics solution. The outer sheath is resistant against high mechanical abuse, particularly to abrasion and
grinding abuse. ÖLFLEX
®
550 P cables are resistant against cuts, microbe proof and hydrolysis resistant.
Application range:
as power cable for construction machinery, stage applications as well as for portable handheld electrical devices
Design
Approvals < 1.0 mm
2
: H05BQ-F
acc. to EN 50525-2-21 resp. VDE 0285-525-2-21 / VDE 0282-10 resp. HD22.10 S2
≥ 1.5 mm
2
: H07BQ-F
acc. to EN 50525-2-21 resp. VDE 0285-525-2-21 / VDE 0282-10 resp. HD22.10 S2
Conductor bare copper, fine wire strand in accordance to IEC 60228 resp. VDE 0295, class 5
Core insulation rubber compound EI 6 acc. to EN 50363-1 resp. VDE 0207-363-1
Core identification acc. to VDE 0293-1, with or without GN/YE ground conductor
up to 5 cored coloured acc. to HD 308 S2 that is VDE 0293-308
Outer sheath Polyurethane compound TMPU, acc. to EN 50363-10-2 resp. VDE 0207-363-10-2
Colour: orange, similar to RAL 2003
Electrical properties
Nominal voltage < 1,0 mm
2
U
0
/U: 300 / 500 V
≥ 1,5 mm
2
U
0
/U: 450 / 750 V
Test voltage Core / Core: 3000 V AC
Mechanical and thermal properties
Min. bending radius for flexible use: 12,5 x outer diameter
fixed installation: 4 x outer diameter
Temperature range occasional flexing: -40 °C up to +90 °C
fixed installation: -40 °C up to +90 °C
Oil resistance acc. to EN 50363-10-2 resp. VDE 0207-363-10-2
Tests acc. to IEC 60811, EN 50395, EN 50396
EC-Directives This cable is conform to the EC-Directives 2006/95/EC (Low Voltage Directive)
and 2011/65/EU (RoHS, Restriction of the use of certain hazardous substances).