4.11 Gas Setup and Adjustment
For the Step by step process to measure CO
2
valuesontheMascotFT,pleaserefertoSteps12
thru Step 22 in Section 4.13 of this Installation Manual.
Table15. CO
2
Values
Table16. Manifold Pressures
WARNING
Installer is required to verify combustion settings as part of
the installation process.
Standard Factory Setting is for MAX Fire. 9.0%
CO
2
@ 0-2,000 ft altitude (Natural Gas).
Customer Service and Product Support: 800.900.9276 • Fax 800.559.1583
Headquarters: 20 Industrial Way, Rochester, NH, USA 03867 • 603.335.6300 • Fax 603.335.3355
1869 Sismet Road, Mississauga, Ontario, Canada L4W 1W8 • 905.238.0100 • Fax 905.366.0130
www.Laars.com Litho in U.S.A. © Laars Heating Systems 1607 Document 4296B
800.900.9276 Fax 800.559.1583 (Customer Service, Service Advisors)
20 Industrial Way, Rochester, NH 03867 603.335.6300 Fax 603.335.3355 (Applications Engineering)
1869 Sismet Road, Mississauga, Ontario, Canada L4W 1W8 905.238.0100 Fax 905.366.0130
www.Laars.com
Document 4296B
Mascot FT, Heating Only, Gas Conversion Kit
pg 3 of 4
Figure C
Table B DIP Switch Settings
MBH 80 100 120 140 N/A 199
9.
Per Table B, set DIP Switch
5 to OFF
for LP Propane.
10.
Turn ON the GAS and WATER supply to the Mascot FT.
11.
Turn ON the Mascot FT.
12.
Connect a manometer to the manifold pressure port. For dual port manometers, use the positive pressure
side. Check for proper manifold gas pressure. Refer to Table C.
ON OFF
MIN Fire Normal Operation
MAX Fire Normal Operation
NG Natural LP Propane
3” Vent Size
2” Vent Size
ON OFF ON OFF ON
ON
OFF ON ON OFF OFF
ON
OFF OFF OFF ON ON
ON
Figure D
Gas Valve for 80 to 140 MBH
Gas Valve for
199 MBH
The gas valve on
the smaller models is
mounted vertically.
Manifold Pressure Port Manifold Pressure Port
DO
NOT
CHANGE
REFERENCE
ONLY.
Table C
Manifold pressure Propane Gas (LP) Natural Gas (NG)
MFTHW 80/100
-0.102
˝
WC -0.102
˝
WC
0.00
˝
WC 0.00
˝
WC
MFTHW 120/140
-0.216
˝
WC -0.216
˝
WC
0.00
˝
WC 0.00
˝
WC
MFTHW 175
-0.169
˝
WC -0.129
˝
WC
-0.015
˝
WC -0.015
˝
WC
MFTHW 199
-0.173WC -0.134
˝
WC
-0.015
˝
WC -0.015
˝
WC
CO
2
value
Propane Gas (LP) Natural Gas (NG)
VENT VENT VENT VENT
MFTHW 80/100
120/140/175/199
9.5~11% 8.5~10.5%
9~10.5 % 8~10%
Refer to the below table.
Manifold pressure Propane Gas (LP) Natural Gas (NG)
MFTHW 80/100
-0.102
˝
WC -0.102
˝
WC
0.00
˝
WC 0.00
˝
WC
MFTHW 120/140
-0.216
˝
WC -0.216
˝
WC
0.00
˝
WC 0.00
˝
WC
MFTHW 175
-0.169
˝
WC -0.129
˝
WC
-0.015
˝
WC -0.015
˝
WC
MFTHW 199
-0.173WC -0.134
˝
WC
-0.015
˝
WC -0.015
˝
WC
CO
2
value
Propane Gas (LP) Natural Gas (NG)
VENT VENT VENT VENT
MFTHW 80/100
120/140/175/199
9.5~11% 8.5~10.5%
9~10.5 % 8~10%
Refer to the below table.
13.
Establish a call for heat. You may need to disconnect the outdoor reset if you are making this gas
conversion during warm weather.
Customer Service and Product Support:
800.900.9276 • Fax 800.559.1583
Headquarters: 20
Industrial Way, Rochester, NH, USA 03867 • 603.335.6300 • Fax 603.335.3355
1869 Sismet Road, Mississauga, Ontario, Canada L4W 1W8 • 905.238.0100 • Fax 905.366.0130
www.Laars.com Litho in U.S.A. © Laars Heating Systems 1607 Document 4296B
800.900.9276 Fax 800.559.1583
(Customer Service, Service Advisors)
20 Industrial Way, Rochester, NH 03867 603.335.6300 Fax 603.335.3355
(Applications Engineering)
1869 Sismet Road, Mississauga, Ontario, Canada L4W 1W8 905.238.0100 Fax 905.366.0130
www.Laars.com
Document 4296B
M
ascot FT, Heating Only, Gas Conversion Kit
pg 4 of 4
Figure E (Conversion label)
14.
Setup your combustion analyser and place the sensor into the combustion test port
15.
Per Table B for Max Fire
,
change dip switch 6 to ON and 7 to OFF. The unit will cycle up to MAX re.
16.
WAIT for your combustion analyser to stabilize. This may take up to 3 minutes depending on your
combustion analyser. Then measure the CO
2
for MAX re. Refer to Table C for acceptable MAX re
combustion readings Do NOT adjust CO2 at MAX Fire. ONLY in MIN Fire, so...
17.
Per Table B for MIN Fire
,
change dip switch 6 to OFF and 7 to ON. The unit will cycle down to MIN Fire.
18.
WAIT for your combustion analyser to stabilize. Then measure the CO
2
for MIN re. Refer to Table D for
acceptable MIN re combustion readings
19.
Open the Gas Valve Adjustment Port by removing the cap screw with a 4mm Allen wrench.
20.
Then use the 4 mm Allen wrench to make a minor adjustment (1/8 turn) to either increase or decrease CO
2
.
21.
It may be necessary to go back and forth between HI Fire and LOW Fire several times (and making
adjustments only at LOW Fire), before CO
2
at both are within acceptable levels. Be sure to put the
adjustment port cap screw back onto the valve when done.
22.
Once the CO
2
and manifold pressure measurements for both MIN and MAX Fire are acceptable per Table
C, set DIP switches 6 and 7 to the OFF position for Nominal Fire (normal operation).
23.
Write in the correct conversion date and the technicians name to the included gas conversion sticker. See
Figure E. Then apply that sticker adjacent to the rating plate.
24.
Put the boiler cover back on and assemble/tighten the 4 screws that hold the cover in place.
This unit was converted on ____/____/___to _____gas
with kit #____________by______________________
(name and company __________________________
accountable)_________________________________
___________________________________________
Cette unité a été converti ____/____/____ten ______gaz
en utilisant le kit numéro _____ par______________
(nom et société_________________________________
responsable)___________________________________
_____________________________________________
H2375200B
Manifold pressure Propane Gas (LP) Natural Gas (NG)
MFTHW 80/100
-0.102
˝
WC -0.102
˝
WC
0.00
˝
WC 0.00
˝
WC
MFTHW 120/140
-0.216
˝
WC -0.216
˝
WC
0.00
˝
WC 0.00
˝
WC
MFTHW 175
-0.169
˝
WC -0.129
˝
WC
-0.015
˝
WC -0.015
˝
WC
MFTHW 199
-0.173WC -0.134
˝
WC
-0.015
˝
WC -0.015
˝
WC
CO
2
value
Propane Gas (LP) Natural Gas (NG)
2˝ VENT 3˝ VENT 2˝ VENT 3˝ VENT
MFTHW 80/100
120/140/175/199
9.5~11% 8.5~10.5%
9~10.5 % 8~10%
Refer to the below table.
Table D
All sizes