Install Instructions

Mascot FT Floor Standing Combination Boiler
Page 69
8.1 Annual startup & general maintenance
Maintenance procedures [Every 6 Months]
- Check the boiler piping (gas and water)
Visually inspect for leaks around internal water
piping. Also inspect external water piping,
circulators, relief valve and ttings. Immediately
call a qualied service technician to repair any
leaks. Leaks must be xed by a qualied service
technician immediately.
Failure to comply with this instruction could result in
severe personal injury, death or substantial property
damage.
- Check the pressure relief valve
WARNING
Leaks must be xed by a qualied service technician
immediately. Failure to comply with this instruction
could result in severe personal injury, death or
substantial property damage. This discharge line
must be installed by a qualied heating installer or a
service technician.
Before proceeding, verify that relief valve outlet has
been piped to a safe place of discharge, avoiding
any possibility of scalding from hot water. If water
ows freely, release the lever and allow the valve
to seat. Watch the end of the relief valve discharge
pipe to ensure that the valve does not weep after
the line has had time to drain. If the valve weeps, lift
the seat again to attempt to clean the valve seat. If
the valve continues to weep, contact your qualied
service technician for inspecting the valve and
system. If water does not ow from the valve even
though you have lifted the lever completely, the valve
or discharge line may be blocked. Shut down the
Combination boiler immediately. Call your qualied
service technician to inspect the combination boiler
and system.
- Check the burner state
You can clean the exterior of burner. However, if you
need to clean the inside of the burner stage, you should
call a qualied service technician.
SECTION 8. Maintenance
A
A
MFTCF 140
MFTCF 199
- Check the air vent
If the air vent valve seems to work freely without
leaking, replace cap “A” by twisting all the way on.
Loosen cap “A” one turn to allow vent to operate.
If vent does not operate correctly, replace the vent.