Specification Sheet

SPECIFICATIONS KWIB1411
COOLING CAPACITY
BTU/hr @ 95F at 60% RH 13,800 (1.1-Ton)
COMPRESSOR DATA
Compressor Type Hermetic Rotary
Operating Temperatures 60-110 F 50%RH
Refrigerant 410A
FAN DATA
Evaporator
Fan Type (Centrifugal) Direct Drive
Air Flow (CFM) 460/3 Speed
Supply Air Device Adjustable Vent
Supply Air Chute Kit (optional) 2 - 5" Dia. x 16" Length
Condenser Water Flow Data
Flow Regulating Valve 1/2"NPT Automatic
Inlet Water 85F-95F Exit (GPM) 3
Inlet Water 75F-95F Exit (GPM) 1.5
Inlet Water 65F-95F Exit (GPM) 1
Inlet Water 55F-95F Exit (GPM) 0.75
ELECTRICAL DATA
Power Supply (Volts) 115/Single Phase
Current Consumption (Amps) 8.6
Power Consumption (kW) 0.9
Maximum Circuit Breaker (Amps) 20
Recommended Breaker Size 15
Minimum Circuit Ampacity (Amps) 16
Min./Max. Voltage 105-125
Power Cord Gauge/Length 14AWG/6'
Plug Configuration NEMA 5-15
DIMENSIONAL DATA
Width x Depth x Height (Inches) 16.325" x 21.75" x 37.25"
Weight (Lbs.) 150
Shipping Weight (Lbs.) 200
SAFETY DEVICE DATA
Compressor Overload Internal
Fan Motor Overload Automatic Internal
Evaporator Freeze Protection Hot Gas Bypass
High Pressure Switch Manual
Low Pressure Switch Automatic
Compressor Short Cycle Yes
Automatic Restart Yes
Thermostat Type Microprocessor/Digital
Condensate Pump Overflow Yes
Condensate Tank Overflow Yes
1-800-KWIKOOL
www.kwikool.com