VIII / Utilizing your KwiKool System
In contrast to conventional air conditioners, which circulate air conditioning capacity evenly
to an entire floor, KwiKool systems are designed for cooling an area with a high concentra-
tion of heat load, usually from electrical or computer equipment. Understanding the capabili-
ties of your KwiKool can help you avoid problems. For example, if you add heat-generating
equipment to the room after purchasing a KwiKool system, you may be short of the
necessary cooling capacity. Your KwiKool system offers an effective affordable solution for
many applications. It can also provide spot cooling for workers or process cooling within a
large space without the use of condenser ducting, such as a warehouse factory, or produc-
tion areas. If the system is used in this manner, the cold air supply must be within 5 feet of
the person or equipment being cooled, since the hot ambient air will mix with the cool air
very quickly. Your KwiKool system is specifically designed to adapt to today’s high tech
environments such as telecommunication or computer rooms and is equipped with the
necessary controls to maintain those special environments. Call your nearest KwiKool
Distributor or 1-800-594-5665 for help or for questions about other applications.
IX / Fault Codes
Your KwiKool Iceberg System incorporates a self-diagnostic system that sounds an audible
alarm, stops your system and displays a fault code to indicate the nature of the problem on
the display panel. See the troubleshooting guide later in this manual for further information.
CF = Condensate Tank Full
AL = High Pressure Switch Tripped
FP = Freeze Protection
X / KPAC II Troubleshooting Guide
Fault Possible Cause Possible Solution
Unit displays CF, Audio
alarm fails to clear on start
up or while operating
Internal Condensate Tank is
full, or condensate float
switch jack is not installed or
not positioned correctly.
Water level switch is
engaged.
Empty Internal Tank (see
section II:B) Unplug tank
plug and reinstall to assure
good connections. System
automatically resets when
fault condition is corrected.
Audio alarm fails to clear on
start up or while operating,
unit displays FP.
Microprocessor has
detected freezing on the
evaporator coil if the system
has a factory installed freeze
sensor. (Special order)
Check for freezing on the
evaporator coil and turn the
system off to let it thaw out,
call 1-800-KWIKOOL if your
system is not equipped with
a freeze sensor. Auto resets
upon correction.