Installation Guide

4. Make the Electrical Connections Canada
WARNING: Risk of electric shock. Make sure the power has been disconnected before performing
the following procedures.
WARNING: Risk of electric shock. Connect the pump and heater (if included) to a properly
grounded, grounding-type Ground-Fault Circuit-Interrupter (GFCI) or Residual Current Device
(RCD). This will provide additional protection against line-to-ground shock hazard.
NOTE: A label identifying the model number and electrical rating of the whirlpool is located near the
whirlpool pump.
Locate and secure each supplied junction box a minimum of 1-1/2 (38 mm) above the subfloor.
The whirlpool controls and system have been prewired at the factory. A qualified electrician should
make a routine service connection to the junction box.
Connect service to the junction box. The 60 Hz model junction box contains line (black) and neutral
(white) wires and a ground lug.
A 120 V, 15 A dedicated circuit is required. Provide a Class A GFCI or RCD.
Provide a separate equipment grounding conductor for the inside ground or ground lug. The
conductor must not be connected to any current-carrying conductor.
Bond in accordance with national and local codes.
Bond in accordance with applicable codes.
Junction Box
NOTE:
The illustrated components may differ
from your actual product.
Bask Power
Supply Cord
From Bask
Power Supply
Ground
Supply from
Branch
Circuit Box
Neutral (White)
From Pump
Ground
Line (Black)
Wire the junction box as shown.
Provide suitable
strain relief.
Wire Connectors
1204118-2-B 8 Kohler Co.