Specification

Standard Features
Model:
38RCLB
Multi-Fuel
Natural Gas/LPG
D Kohler Co. provides one-source responsibility for the
generating system and accessories.
D The generator set and its components are prototype-tested,
factory-built, and production-tested.
D The generator set accepts rated load in one step.
D A standard five-year or 2000 hour limited warranty covers all
systems and components.
D Quick-ship (QS) models with selected features are available.
See your Kohler distributor for details.
D RDC2 Controller
d One digital controller manages both the generator set and
transfer switch functions (with optional Model RXT
transfer switch).
d Designed for today’s most sophisticated electronics.
d Electronic speed control responds quickly to varying
household demand.
d Digital voltage regulation protects your valuable
electronics from harmonic distortion and unstable power
quality.
d Two-line, backlit LCD screen is easy to read in all lighting
conditions, including direct sunlight and low light.
D Engine Features
d Powerful and reliable 2.2 L turbocharged liquid-cooled
engine
d Electronic engine management system.
d Simple field conversion between natural gas and LPG
fuels while maintaining emission certification.
D Innovative Cooling System
d Electronically controlled fan speeds minimize generator
set sound signature.
D Certifications
d The 60 Hz generator set engine is certified by the
Environmental Protection Agency (EPA) to conform to the
New Source Performance Standard (NSPS) for stationary
spark-ignited emissions.
d UL 2200/cUL listing is available (60 Hz only).
d CSA certification is available (60 Hz only).
d Accepted by the Massachusetts Board of Registration of
Plumbers and Gas Fitters.
D Approved for stationary standby applications in locations
served by a reliable utility source.
The Kohler
r
Advantage
D High Quality Power
Kohler home generators provide advanced voltage and
frequency regulation along with ultra-low levels of
harmonic distortion for excellent generator power quality to
protect your valuable electronics.
D Extraordinary Reliability
Kohler is known for extraordinary reliability and
performance and backs that up with a premium five-year or
2000 hour limited warranty.
D All-Aluminum Sound Enclosure
D Quiet Operation
Kohler home generators provide quiet, neighborhood-
friendly performance.
G4-262 (38RCLB) 4/16a
Generator Set Ratings
Alternator Voltage Ph Hz
Standby Ratings
Natural Gas LPG
kW/kVA Amps kW/kVA Amps
4E8.3
120/240 1 60 38/38 158 38/38 158
4D8.3
120/208 3 60 38/47 132 38/47 132
127/220 3 60 38/47 125 38/47 125
120/240 3 60 38/47 114 38/47 114
277/480 3 60 38/47 57 38/47 57
220/380 *
3 50 30/38 58 31/39 59
230/400 3 50 30/38 55 31/39 56
240/416 * 3 50 30/38 53 31/39 54
* 50 Hz models are factory-connected as 230/400 volts. Field-adjustable to 220/380 or 240/416 volts by an authorized service technician.
RATINGS: All three-phase units are rated at 0.8 power factor. All single-phase units are rated at 1.0 power factor. Due to manufacturing variations, the ratings tolerance is ±5%. Standby Ratings: Standby
ratings apply to installations served by a reliable utilit y source. The standby rating is applicable to varying loads with an average load fact or of 80% for the duration of a power outage. No overload capacity
is specified for this rating. Ratings are in accordance with ISO-3046/1, BS 5514, AS 2789, and DIN 6271. GENERAL GUIDELINES FOR DERATI NG: Altitude: Derate 1.3% per 100 m (328 ft.) elevation above
200 m (656 ft.). Temperature: Derate 3.0% per 10_C(18_F) temperature above 25_C(77_F). Availability is subject to change without notice. The generator set manufacturer reserves the right to change the
design or specificat ions without notice and without any obligation or liability whatsoever . Contact your local Kohler generator distributor for availability.

Summary of content (4 pages)