Product Overview

Description and Application
The CTE-5100 Electronic Room Thermostat series
is designed for use with the CSP-5001/5002 Flow
Controller-Actuator and/or the REE-1000/4000 series
auxiliary relays. Other high impedance (10K ohms
or higher) controls, such as MEP series actuators and
VEB series valves requiring a 0 to 10 VDC control
circuit, may be controlled via any of the CTE-5100
series thermostats. The CTE-5100 series thermostats
have both limited and non-limited outputs. The lim-
ited output is used to provide adjustable minimum
and maximum limits to a CSP-5001/5002 or impose
electronic limits to a proportional actuator or valve.
Models are available for cooling, heating, cooling
with reheat, cooling/heating changeover, day/night,
or night/day applications. Temperature averaging
and/or overrides are also available.
All thermostats require a scale plate assembly and
cover, which may be ordered separately or as part
of a value package containing the most frequently
ordered accessories (see the Accessories and Value
Packages sections). Thermostat and accessories styl-
ing feature the setpoint indicator and/or thermom-
eter to be visible or concealed, setpoint adjustment
locked or restricted, vertical or horizontal mounting,
and aractive color nishes in plastic or metal.
Features
Available for cooling, heating, cooling w/re heat,
cooling/heating changeover, day/night, or night/
day applications
Single or dual setpoint models
Outputs w/ adjustable min./max. limits or no limits
Visible or hidden setpoint indicator
Models
The following models are available (scale plates and
covers are not included—see Accessories):
CTE-5101 Single setpoint, direct acting
CTE-5103 Dual setpoint, DA and RA
CTE-5104 Dual setpoint, direct and reverse
acting (no T4 output)
Specifications and design subject to change without notice.
CTE-5100 Series
Electronic Room Thermostat
Specifications
Supply Voltage 16 VDC (9 mA) (14 to 20 VDC)
Output Range 0 to 10 VDC
Temperature Range 55 to 85° F (13 to 29° C)
Proportional Band
CTE-5101/5103 2° F (1.1° C) w/ limits output
(T1/T2)
4° F (2.2° C) w/o limits output
(T3/T4)
CTE-5104 2° F (1.1° C) w/ and w/o limits
output (T1/T2/T3)
Thermostat Action
CTE-5101 Direct Acting (DA) T1/T3
CTE-5103 Direct Acting (DA) T1/T3
Reverse Acting (RA) T2/T4
CTE-5104 Direct Acting (DA) T1/T3
Reverse Acting (RA) T2
Connections Wire clamp type, 14-22 AWG
Base Material Black ame-retardant plastic
Size (With cover) 2-9/16 x 3-7/16 x
1-7/8" (65 x 87 x 47 mm)
Weight 3.0 oz. (85 grams)
Approvals SASO PCP Registration KSA
R-103263
Temperature Limits
Operating 40 to 120° F (4 to 49° C)
Shipping –40° to 140° F (–40 to 60° C)
(Shown with
Horizontal
Scale Plate
and Light
Almond
Cover
Installed)
Description and Application 1
Features 1
Specifications 1
Accessories 2
Value Packages 2
Dimensions and Details 2
NOTE: For graphs and information on CTE-5100
mounting, wiring, calibration, and sample
applications, see the CTE-5100 Installation
Guide and the CSP-5001/5002 Applica-
tions Guide.

Summary of content (2 pages)