Converting Digital Data to Voltage or Current Values to be Output
To output digital data as analog data, the voltage and current values that are to be
output from the KV-DA4 are first converted to the corresponding digital data by the
sequence program, and written to the data memory for D/A conversion. Voltage and
current values cannot be written to the data memory for D/A conversion as they are.
For details on the voltage/digital data conversion tables, see "9.4.3 A/D and D/A Conversion Tables"
on page 1-357. For details on sample programs, see "9.5 Programming Examples" on page 1-359.
For details on data memory for D/A conversion, see "9.4.3 A/D and D/A Conversion Tables" on page
1-357.
Note: When making a sequence program, take care not to exceed the output range
(0 to 4095). If a value exceeding this range is written to the data memory for D/A
conversion, unsteady values will be output from the KV-DA4.
How to calculate digital data when outputting analog voltage
Digital data = (output voltage (mV)
÷ resolution (5 mV)) + offset value (2000)
Example
When outputting +7.5 V
(7500 (mV) ÷ 5 (mV)) + 2000 = 3500
Write "3500" to D/A conversion memory.
Next, turn ON the special utility relay for D/A conversion.