RTD temperature probe
Description Standard Measuring range Measuring accuracy
a
a
The accuracy values refer to the maximum measuring range. Smaller measuring ranges lead to reduced linearization accuracy.
Ambient
temperature influence
Pt50
Two-wire circuit
Three-wire circuit
DIN EN 60751 -200 to +850 °C 0.05 % 50 ppm/K
Cu50
Two-wire circuit
Three-wire circuit
IEC 60 317 -50 to +200 °C 0.15 % 50 ppm/K
Pt100
Two-wire circuit
Three-wire circuit
DIN EN 60751 -200 to +850 °C 0.05 % 50 ppm/K
Pt500
Two-wire circuit
Three-wire circuit
DIN EN 60751 -200 to +850 °C 0.1 % 50 ppm/K
Pt1000
Two-wire circuit
Three-wire circuit
DIN EN 60751 -200 to +850 °C 0.1 % 50 ppm/K
Ni100
Two-wire circuit
Three-wire circuit
DIN 43760 -60 to +250 °C 0.15 % 50 ppm/K
Ni1000
Two-wire circuit
Three-wire circuit
DIN 43760 -60 to +250 °C 0.1 % 50 ppm/K
KTY11-6
Two-wire circuit
-50to+15C 1% 50 ppm/K
Pt50
Two-wire circuit
Three-wire circuit
GOST 6651-99 -200 to +850 °C 0.05 % 50 ppm/K
Pt100
Two-wire circuit
Three-wire circuit
GOST 6651-94 -200 to +850 °C 0.05 % 50 ppm/K
Cu50
Two-wire circuit
Three-wire circuit
GOST 6651-94 -50 to +200 °C 0.15 % 50 ppm/K
Cu100
Two-wire circuit
Three-wire circuit
GOST 6651-94 -50 to +200 °C 0.15 % 50 ppm/K
Smallest measuring span 15 K
Measuring current Pt100 approx. 250 μA, Pt1000 approx. 100
μA
Sensor lead resistance Max. 10 Ω per cable for two-wire and three-wire circuits
Lead compensation Not required for a three-wire circuit. For a two-wire circuit, the lead compensation can
be compensated for in the software by correcting the process value.
Measuring range start/end Freely programmable within the limits in steps of 0.1 K
Sampling rate Controller 1(2): 150 ms in total
Input filter Digital filter, 2nd order; filter time constant can be set from 0 to 100 s
Special features Can also be programmed in °F