Contents 1 General Information 1.1 Overview 1.3 Warnings 1 2 2. Installation 5 2.1 Installation safety 5 6 6 6 7 8 9 1.2 Applicable Products 2.2 Installation Condition 2.2.1 Climate condition 2.2.2 Site selection 2.2.3 Tilt angle selection 2.3 Mechanical Installation introduction 2.3.1 Fixation with screws 2.3.3 Fixation with clamps at short sides of the frames 12 14 2.3.
1. General Information 1.1 Overview Thanks for choosing Jinko Solar PV modules. In order to ensure the PV modules are installed correctly, please read the following installation instructions carefully before modules are installed and used. Please remember that these products generate electricity and certain safety measures need to be taken to avoid danger. 1.
(xxx=200~330,in increment of 5) JKMxxxM-60L-V JKMxxxM-60BL-V (xxx=300~330,in increment of 5) Group 8 JKMxxxM-60H-V JKMxxxM-60HB-V (xxx=200~340,in increment of 5 ) JKMxxxM-60HL-V JKMxxxM-60HBL-V (xxx=300~340,in increment of 5 ) Notes: ① V: Module with 1500V ② PP: the eagle series module ③ Plus: the eagle+ series module ④ W: module with metal support bar ⑤ H: Half-cut series module ⑥ J4: the eagle black Series module ⑦ L:large cell series module Make sure the module array is designed in such a way not t
Artificially concentrated sunlight shall not be directed on the module or panel. Front protective glass is utilized on the module. Broken solar module glass is an electrical safety hazard (may cause electric shock or fire). These modules cannot be repaired and should be replaced immediately.
Do not remove any part installed by Jinko Solar or disassemble the module. All instructions should be read and understood before attempting to install, wire, operate and maintain the module. Don‟t lift up PV modules using the attached cables or the junction box. All PV systems must be grounded to earth. If there is no special regulation, please follow the National Electrical Code or other national code.
During all transportation situations, never drop the module from a vehicle, house or hands. This will damage the module. Do not clean the glass with chemicals. Only use tap water. Make sure the module surface temperature is cool to the touch. Cleaning modules with cool water when module surface temp is high may result in glass breakage. Do not disconnect any of the modules when under load. The recommended standoff height is 15cm.
Do not touch the junction box and the end of the interconnect cables (connectors) with bare hands during installation or under sunlight, regardless if the PV module is connected to or disconnect from the system. Do not expose the PV module to excessive loads on the surface of the PV module or twist the frame. Do not hit or put excessive load on the glass or back sheet, this may break the cells or cause micro cracks.
When solar modules are used to charge batteries, the battery must be installed in a manner, which will protect the performance of the system and the safety of its users. Follow the battery manufacturer‟s guidelines concerning installation, operation and maintenance recommendations. In general, the battery (or battery bank) should be away from the main flow of people and animal traffic. Select a battery site that is protected from sunlight, rain, snow, debris, and is well ventilated.
2.3 Mechanical Installation introduction Solar PV modules usually can be mounted by using the following methods: bolts and clamps. ﹡Note: (1) All installation methods herein are only for reference, and Jinko Solar will not provide related mounting components, the system installer or trained professional personnel must be responsible for the PV system‟s design, installation, and mechanical load calculation and security of the system.
2.3.1 Fixation with bolts The frame of each module has 8 mounting holes (Length* Width: 14mm*9mm) used to secure the modules to support structure. You can use the four symmetry holes close to the inner side on module frame. If excessive wind or snow load are expected, you must use all the eight mounting holes. The module frame must be attached to a mounting rail using M8 corrosion-proof bolts together with spring washers and flat washers in eight symmetrical locations on the PV module.
Figure 2 above: Normal PV module installed with Bolt fitting method - 10 -
Figure 3 above: Half-cut PV module installed with Bolt fitting method - 11 -
2.3.2 Fixation with clamps The applicable products only allow using clamps at long side of frames. The module clamps should not come into contact with the front glass and must not deform the frame. Be sure to avoid shadowing effects from the module clamps. The module frame is not to be modified under any circumstances. When choosing this type of clamp-mounting method, please be sure to use at least four clamps on each module, two clamps should be attached on each long side of the module.
Module type Cell type Cell quantity Group 1 Poly Group 3 Dimension(mm) A*B J K 6*12 1956*992 & 1979*1002 400 480 Poly 6*10 1650*992 & 1665*1002 400 420 Group 5 Mono 6*12 1956*992 & 1979*1002 400 480 Group 7 Mono 6*10 1650*992 & 1665*1002 400 420 Table 1 above: Mechanical dimensions when modules installed at long side with Clamp 2)Half-cut Figure 5: half-cut installed at long side with Clamp fitting method Module type Cell type Cell quantity Group 2 6 inch Poly Group 6 D
Clamp type Dimension Fringe Clamp(40 mm thickness) 39 x 50 x 42 mm Fringe Clamp(35 mm thickness) 41.5 x 50 x 40 mm Middle Clamp 42 x 50 x 28 mm Composition material Aluminum-alloy Table 3 above: The specification & material of clamp Clamp type Middle Clamp Dimension(mm) Q O R P 13.5 0.5~2 15 2.5 Table 4 above: Mechanical dimensions when modules installed with mid Clamp 2.3.
Figure 6 above: PV module installed at short side with Clamp fitting method Module type Cell type Group 1 Group 5 Group 3 Group 7 6 inch Poly 6 inch Mono 6 inch Poly 6 inch Mono Cell quantity 6*12 6*12 6*10 6*10 Dimension(mm) A*B J K Frame 1956*992 & 1979*1002 50 240 40*35 & 35*35 1956*992 & 1979*1002 50 240 40*35 & 35*35 1650*992 & 1665*1002 50 240 40*35 1650*992 &1665*1002 50 240 40*35 Table 5 above: Mechanical dimensions when modules installed at short side with Clamp fitting method 2)Half-cut Fi
8 & 9. The mounting place distance is suggested bigger than J and less than K for short sides,bigger than M and less than N for long sides, as shown below.
2)Half-cut Figure 9: PV module installed at long and short side with Clamp fitting method Dimension(mm) Module type Cell type Cell quantity A*B J K M N Frame Group 2 6 inch Poly 6*24 1987*992 & 2000*992 & 2008*1002 50 240 400 480 40*35 & 35*35 Group 4 6 inch Poly 6*20 1665*992 & 1684*1002 50 240 400 420 40*35 & 35*35 Group 6 6 inch Mono 6*24 1987*992 & 2000*992 & 2008*1002 50 240 400 480 40*35 Group 8 6 inch Mono 6*20 1665*992 & 1684*1002 50 240 400 420 40*35
and local electrical codes and standards, make sure the modules strings in parallel are protected with the appropriate in-line string fusing. d) Open the combiner box of the control system and connect the conductors from the PV arrays to the combiner box in accordance with he design and local codes and standards.
Grounding Clip Model series Group 1~Group 12 Manufacturer Type Tyco Electronics Corp 1954381-1 g) Follow the requirements of applicable local and national electrical codes. h) These modules contain factory installed bypass diode. If these modules are incorrectly connected to each other, the bypass diodes, cable or junction box may be damaged. i) The module shall wire in accordance with the NEC, the grounding method of the frame of arrays shall comply with the NEC, article 250.
f) When cleaning the modules, it is not allowed to stand on the module. See below pictures shown, this is prohibited. g) Never use chemicals when cleaning modules as this may affect the module warranty and energy output. 5. Electrical specification The module electrical rating are measured under Standard Test Conditions, which are 1000W/m2, irradiance with AM 1.5 spectrum and 25 deg (77°F) ambient temperature.
5.1 Electrical Specifications – Group 1 & 2 – Polycrystalline Modules (Refer to 1.2 “Applicable Products” for specific module type). Module Type xxx = Group 1 and Group 2 250 255 260 265 270 275 280 285 290 295 300 305 250 255 260 265 270 275 280 285 290 295 300 305 34.2 34.5 34.7 34.9 35.0 35.2 35.3 35.5 35.8 36.2 36.6 36.8 7.31 7.39 7.49 7.59 7.71 7.81 7.93 8.03 8.11 8.15 8.20 8.30 43.5 43.7 43.9 44.1 44.2 44.4 44.5 44.7 44.9 45.1 45.3 45.6 8.
Module Type xxx = Group 1 and Group 2 Group 2 310 315 320 325 330 335 340 345 350 355 360 365 370 310 315 320 325 330 335 340 345 350 355 360 365 370 37.0 37.2 37.4 37.6 37.8 38 38.2 38.4 38.6 38.9 39.1 39.3 39.5 8.38 8.48 8.56 8.66 8.74 8.82 8.9 8.98 9.07 9.12 9.21 9.29 9.37 45.9 46.2 46.4 46.7 46.9 47.2 47.5 47.8 48 48.2 48.5 48.8 49.1 8.96 9.01 9.05 9.1 9.14 9.18 9.22 9.29 9.36 9.43 9.51 9.58 9.
5.2 Electrical Specifications – Group 3 & 4 – Polycrystalline Modules (Refer to 1.2 “Applicable Products” for specific module type). Module Type xxx = Group 3 and Group 4 200 205 210 215 220 225 230 235 240 245 250 255 200 205 210 215 220 225 230 235 240 245 250 255 28.2 28.4 28.6 28.8 29.0 29.2 29.4 29.6 29.8 30.1 30.5 30.8 7.09 7.22 7.34 7.47 7.59 7.71 7.82 7.94 8.06 8.14 8.20 8.28 35.3 35.5 35.8 36.1 36.3 36.6 36.8 37.0 37.3 37.5 37.7 38.0 8.
Module Type xxx = Group 3 and Group 4 Group 4 260 265 270 275 280 285 290 295 300 305 310 260 265 270 275 280 285 290 295 300 305 310 31.1 31.4 31.7 32.0 32.3 32.5 32.8 33.1 33.4 33.6 33.9 8.37 8.44 8.52 8.61 8.69 8.77 8.86 8.95 9.03 9.11 9.19 38.1 38.6 38.8 39.1 39.4 39.6 39.8 40.1 40.3 40.6 40.8 8.98 9.03 9.09 9.15 9.20 9.26 9.32 9.37 9.43 9.49 9.
5.3 Electrical Specifications – Group 5 & 6 – Polycrystalline Modules (Refer to 1.2 “Applicable Products” for specific module type). Module Type xxx = Group 5 and Group 6 250 255 260 265 270 275 280 285 290 295 300 305 310 250 255 260 265 270 275 280 285 290 295 300 305 310 34.8 35.0 35.3 35.6 35.9 36.1 36.3 36.5 36.7 36.8 37.0 37.2 37.4 7.18 7.29 7.37 7.44 7.52 7.62 7.71 7.81 7.90 8.02 8.11 8.20 8.29 43.4 43.6 43.9 44.1 44.4 44.6 44.8 45.0 45.
Module Type xxx = Group 5 and Group 6 315 320 325 330 335 340 345 350 355 360 365 370 375 380 315 320 325 330 335 340 345 350 355 360 365 370 375 380 37.6 37.8 38.0 38.2 38.4 38.7 38.9 39.1 39.3 39.5 39.7 39.9 40.2 40.5 8.38 8.47 8.55 8.64 8.72 8.79 8.87 8.94 9.04 9.12 9.20 9.28 9.33 9.39 46.1 46.3 46.5 46.7 46.9 47.1 47.3 47.5 47.8 48.0 48.2 48.5 48.7 48.9 8.87 8.95 9.03 9.11 9.18 9.24 9.31 9.38 9.45 9.51 9.57 9.61 9.68 9.
Module Type xxx = Group 5 and Group 6 Group 6 385 390 395 400 405 410 385 390 395 400 405 410 40.8 41.1 41.4 41.7 42.0 42.3 9.44 9.49 9.55 9.6 9.65 9.69 49.1 49.3 49.5 49.8 50.1 50.4 9.92 10.12 10.23 10.36 10.48 10.60 Maximum Power at STC (Pmax, Wp) Maximum Power Voltage (Vmp, V) Maximum Power Current (Imp, A) Open-circuit Voltage (Voc, V) Short-circuit Current (Isc, A) Maximum system 1500VDC Voltage Normal PV module :1956x992x40mm (77.01×39.05 x1.
5.4 Electrical Specifications – Group 7 & 8 – Polycrystalline Modules (Refer to 1.2 “Applicable Products” for specific module type). Module Type xxx = Group 7 and Group 8 200 205 210 215 220 225 230 235 240 245 250 255 260 265 200 205 210 215 220 225 230 235 240 245 250 255 260 265 28.8 29.0 29.2 29.3 29.5 29.7 29.9 30.0 30.2 30.4 30.6 30.8 30.9 31.2 6.94 7.07 7.19 7.34 7.46 7.57 7.69 7.83 7.95 8.06 8.17 8.28 8.42 8.50 36.5 36.6 36.7 36.8 36.
Module Group 7 and Group 8 Type xxx = Group 8 275 280 285 290 295 300 305 310 315 320 325 330 335 340 275 280 285 290 295 300 305 310 315 320 325 330 335 340 31.6 31.8 32.0 32.2 32.4 32.6 32.8 33.0 33.2 33.4 33.6 33.8 34.0 34.2 8.70 8.81 8.90 9.02 9.10 9.21 9.30 9.4 9.49 9.59 9.68 9.77 9.87 9.96 38.5 38.6 38.7 39.5 39.7 40.1 40.3 40.5 40.7 40.9 41.1 41.3 41.5 41.7 9.40 9.49 9.51 9.55 9.61 9.72 9.83 9.92 10.0 10.1 10.
6. Disclaimer of Liability Because the use of the manual and the conditions or methods of installation, operation, use and maintenance of photovoltaic (pv) product are beyond Jinko‟s control, Jinko does not accept responsibility and expressly disclaims liability for loss, damage, or expense arising out of or in any way connected with such installation, operation, use or maintenance.
Note _________________________________________________________________________ _________________________________________________________________________ _________________________________________________________________________ _________________________________________________________________________ _________________________________________________________________________ _________________________________________________________________________ - 31 -
7. Contact us Jinko Solar Co., Ltd. (Shanghai Office) Jinko Building, #99 Shouyang Road, Jingan District, Shanghai, China Postcode: 200127 Tel :(86)-21-51838777 Fax :(86)-21-51808600 Jinko Solar Co., Ltd. (Jiangxi Manufacture base) No.1 Jinko Road, Shangrao Economic Development Zone, Jiangxi Province, China Postcode: 334100 Tel:(86)-793-8588188 Fax:(86)-793-8461152 Jinko solar Import and Export co.
Global Sales & Marketing Center Jiangxi Manufacture Base Zhejiang Manufacture Base Jinko Building #99 Shouyang Road, Jingan District, Shanghai, China 200027 Tel: +86 21 5183 8777 Fax: +86 21 5180 8600 No.1 Jinko Road, No.58 Yuanxi Road, Shangrao Economic Development Zone, Haining Yuanhua Industrial Park, Jiangxi Province, China 334100 Zhejiang Province, China 314416 Tel:+86 793 858 8188 Tel: +86 573 8798 5678 Fax:+86 793 846 1152 Fax: +86 573 8787 1070 www.jinkosolar.