Connecting and Configuring the Module and Instrument
TDC
-1346-000 100T-HON Honeywell Telemetry Module Installation Guide 22
Proprietary and Confidential
To connect the 100T-HON telemetry module to the Mini-Max Mercury Instrument
Note If the 100T-HON telemetry module will be connected to the Honeywell Mini-Max, the module
must have an RS232 connection to the instrument. (Optional) The module connection to the Mini-Max
may be a mechanical uncorrected volume pulser connection.
1. RS232 Terminal Block
2. Compression Connector
3. Pulser Board
Note For more information about routing the cable through the compression connector and stripping the
cable's outer jacket, refer to To connect the 100T-HON telemetry module to the Mini-AT Mercury
Instrument on page 19
.
1. Insert the 100T-HON telemetry module cable into the instrument's compression connector.
2. Strip five inches of the outer insulation from the 100T-HON telemetry module cable.
3. Individually strip 1/4-inch individual wire insulation from the red, white, yellow, black, and green lead
wires.
Warning Strip wires one at a time to prevent shorting stripped wires.