Instructions / Assembly

Termination kits must be tested and certified for
use with whatever brand of heating appliance
and pipe-fitting-cement system is used. IPEX
termination kits such as the Low Profile are fully
certified for use with IPEX product only.
System 636 PVC Low Profile vent kits are made
from certified compound and are rated to 65ºC
maximum.
The vent termination must maintain all termination clearances and be installed
in accordance with local building code and CSA B149.1 Natural Gas and
Propane Installation Code. (see Figure 5)
Installation Procedure
1. Once the proper location has been determined, cut 2 holes in the wall
large enough to accommodate the pipe. Pipe diameters and distance
between hole centers can be found in Table 3.
2. Slide both the intake and vent pipes through the holes. Solvent weld both pipes to the base of the vent termination kit, following the
solvent welding procedures outlined in this guide. (see Figure 7)
System 636 Installation Methods
25
Item # Description Pipe O.D.
Hole Spacing
(ctr to ctr)
196984 2" Flush Mount Vent Kit 2.375" 5.6"
196985 3" Flush Mount Vent Kit 3.5" 5.6"
196986 4" Flush Mount Vent Kit 4.5" 5.6"
TABLE 3 – Low Profile Termination Kits Dimensions
TABLE 4 – Each Kit Contains:
Qty Item Description
1 Base (two holes)
1 Cap (one hole)
8 Stainless Steel Screws
4 Plastic Anchors
Low Profile Side Wall Termination Kit