User Guide

15
www.insigniaproducts.com
8 Cu. Ft. Electric and Gas Dryers
INSTALLATION INSTRUCTIONS
Exhausting requirements
WARNING:
Do not exhaust your dryer into a chimney, a wall, a ceiling, an attic, a crawl
space, or a concealed space in a building.
Your dryer must be exhausted to the outside to reduce the risk of fire when
installed in an alcove or closet.
WARNING:
NEVER USE A PLASTIC OR NON-METAL FLEXIBLE DUCT
If your existing duct work is plastic, non-metal, or combustible, replace it with
metal before installing this dryer.
Use only a metal exhaust duct that is non-flammable to ensure containment
of the exhaust air heat and lint.
See "Duct requirements" on page 16 for the maximum duct length and
number of elbows.
All dryers must be exhausted outside.
Do not assemble the duct with screws or other fasteners that extend into the
duct or that catch lint.
The exhaust duct should be 4 in. (10.2 cm) in diameter.
The total length of flexible metal duct should not exceed 7.8 ft. (2.4 m).