User's Manual

MorphoAccess® SIGMA Extreme Series - Installation Guide
Section 3 : Installation Procedure
2017_2000024418 - Draft
V0
January 2017
This document and the information therein are the property of Safran Identity & Security.
They must not be copied or communicated to a third party without the prior written authorization of Safran
29
Installation
Required tools (not supplied)
Six (6) raw plugs + six (6) screws ø4mm max and length adapted to the wall
material.
One (1) screwdriver adapted to screws above.
One (1) Drill (with a drill bit diameter adapted to raw plugs above).
One (1) hole saw (depending on installation case).
A (1) Torx T20 screwdriver
Deadbolt/door strike
Snubber diode required to protect regulated DC power supply from inductive
kickback (1N4007 diode or equivalent recommended)
Separate power supply for the deadbolt/door strike based on supplier's
recommendations.
External relay (if required)
Networking cable
For UL-294 compliance, an earthed screen in the wire or around all wires to/from
product is only required when the wires share space/compartment/tube with high
voltage cables.
Equipment from the initial package to use
One (1) Terminal’s body.
One (1) wall plate.