User manual

ARTIKELNUMMER
12.321.15.3xx
Auswahl des Gerätetyps
12 ohne Phasenfolgeüberwachung
13 mit Phasenfolgeüberwachung
ZDV
H S B
ZDV
H S B
ZDV
H S B
ZDV
H S B
L1
L2
L3
Rechtsdrehfeld
alle LED´s leuchten
Relais ist angezogen alle
Werte i.O.
Linkssdrehfeld
alle LED´s blinken in
falscher Reihenfolge
Phasenausfall
entsprechende LED
erlischt
Unterspannung /
Überspannung /
entsprechende LED
blinkt
0s
10s
270
230
t
U>
250
230
190
U<
210
L1
L2
L3
0s
10s
270
230
t
U>
250
230
190
U<
210
L1
L2
L3
0s
10s
270
230
t
U>
250
230
190
U<
210
L1
L2
L3
0s
10s
270
230
t
U>
250
230
190
U<
210
ZDV
H S B
Asymetriefehler /
Frequenzfehler :
alle LED´s blinken
gleichzeitig
L1
L2
L3
0s
10s
270
230
t
U>
250
230
190
U<
210
Messrelais
Drehstrommessrelais ZDV/ZDV-P
Baureihe 17,5mm mit 1 Wechsler
measuring relay
ZDV/ZDV-P phase measuring relay
type 17,5mm with 1 changeover
ANWENDUNG
Zur Überwachung der Spannungswerte, Phasenausfall
und D r e h f e l d von D r e h s t r o m n e t z e n , sowie
Überwachung von Wechselstromnetzen auf
Spannungswerte.
BESCHREIBUNG
Das Gerät überwacht die drei Phasen eines Drehstrom-
netzes auf Phasenausfall, Unterspannung, Über-
spannung und je nach Variante auf Rechtsdrehfeld. Das
Gerät bezieht seine Versorgungsspannung aus allen drei
Phasen und N bzw. PEN.
Das Anliegen der einzelnen Phasen wird durch separate
LED´s angezeigt.
FUNKTION
Das Messrelais schaltet in seine Arbeitsstellung sobald alle
drei Phasen innerhalb der eingestellten Werte sind. Dieser
Zustand wird durch das Leuchten der drei LED´s angezeigt.
Unter- oder überschreitet mindestens eine der drei Phasen
die eingestellte Spannung, so fällt des Relais nach Ablauf
der eingestellten Verzögerungszeit in seine Ruhelage
zurück.
Zur Überwachung von Wechselstromnetzen mit 230V
Versorgungsspannung müssen die Phasenanschlüsse L1
und L2 gebrückt werden und L3 darf nicht angeschlossen
werden. Ebenso ist hierzu ein Neutralleiteranschluss
notwendig.
BETRIEBSZUSTANDSANZEIGEN
APPLICATION
Monitoring of correct rotation, phase loss and voltage
protection (207-253V) of three-phase systems.
Or to protect a single phase system (L1-N).
DESCRIPTION
The phase measuring relay measures each of the three
phases for phase sequence, phase loss, undervoltage
and overvoltage. The relay is powered from all three
phases and the neutral conector.
Each phase has its own led which indicates the status.
FUNCTION
The measuring relay switches into its work position as soon
as all three phases are between the adjusted values and
(depending to the unit) the phase sequence turns clockwise.
This status is indicated by all three red leds. The relay
switches into its rest position if at least one of the phases is
not in the correct voltage value or (depending to the unit) a
counter clockwise rotation occurs. To monitor a possible
counter clockwise rotation, simply switch the connections of
two of the three phases.
To protect a single phase system with only one power line
230V it is necessary to bridge the connectors L1 and L2 and
L3 must be free.
INDICATORS
|H|S|B| Industrieelektronik GmbH
Hans-Bördlein-Str. 10
97723 Oberthulba/Germany
Tel.: +49 9736 / 75759 - 0
Fax: +49 9736 / 75759 - 20
info@hsb-electronics.de
www.hsb-electronics.de
Industrieelektronik GmbH
| | | |
H S B
ZDV
H S B
ZDV
H S B
ZDV
H S B
ZDV
H S B
L1
L2
L3
clockwise rotation
all lamps are on
relay is engergised
wrong rotation
the lamps rotate
relay is of
f
phase loss
the individual lamp is off
relay is of
f
under- overvoltage
failure
the individual lamp is
flashing, relay is of
f
0s
10s
270
230
t
U>
250
230
190
U<
210
L1
L2
L3
0s
10s
270
230
t
U>
250
230
190
U<
210
L1
L2
L3
0s
10s
270
230
t
U>
250
230
190
U<
210
L1
L2
L3
0s
10s
270
230
t
U>
250
230
190
U<
210
ZDV
H S B
Asymetry /
frequency failure :
all lamps flashing
L1
L2
L3
0s
10s
270
230
t
U>
250
230
190
U<
210
PART NUMBER
12.321.15.3xx
Choose your type
12 without phase sequence protection
13 with phase sequence protection

Summary of content (2 pages)