ProLiant ML350 Gen10 Server

QuickSpecs
HPE ProLiant ML350 Gen10 Server
Technical Specifications
Page 55
Extended Ambient Operating
Temperature
For approved hardware configurations, the supported system
inlet range is extended to be: 5° to 10°C (41° to 50°F) and 35°
to 40°C (95° to 104°F) at sea level with an altitude derating of
1.0°C per every 175 m (1.8°F per every 574 ft) above 900 m
(2953 ft) to a maximum of 3050 m (10,000 ft). The approved
hardware configurations for this system are listed at the URL:
http://www.hpe.com/servers/ashrae
For approved hardware configurations, the supported system
inlet range is extended to be: 40° to 45°C (104° to 113°F) at
sea level with an altitude derating of 1.0°C per every 125 m
(1.8°F per every 410 ft) above 900 m (2953 ft) to a maximum
of 3050 m (10,000 ft). The approved hardware configurations
for this system are listed at the URL:
http://www.hpe.com/servers/ashrae
System performance may be reduced if operating in the
extended ambient operating range or with a fan fault.
Non-operating
-30° to 60°C (-22° to 140°F). Maximum rate of change is
20°C/hr (36°F/hr).
Relative Humidity
Operating
8% to 90% - Relative humidity (Rh), 28°C maximum wet bulb
temperature, non-condensing.
(non-condensing)
Non-operating
5 to 95% relative humidity (Rh), 38.7°C (101.7°F) maximum
wet bulb temperature, non-condensing..
Altitude
Operating
3050 m (10,000 ft). This value may be limited by the type and
number of options installed. Maximum allowable altitude
change rate is 457 m/min (1500 ft/min).
Non-operating
9144 m (30,000 ft). Maximum allowable altitude change rate is
457 m/min (1500 ft/min).
Acoustic Noise
Listed are the declared A-Weighted sound power levels (L
WAd
) and declared average bystander position
A-Weighted sound pressure levels (L
pAm
) when the product is operating in a 23°C ambient environment.
Noise emissions were measured in accordance with ISO 7779 (ECMA 74) and declared in accordance
with ISO 9296 (ECMA 109). The listed sound levels apply to standard shipping configurations.
Additional options may result in increased sound levels, for example, higher-
end graphic processing units
(GPU), NVMe SSD or NVMe M.2
. Please have your HPE representative provide information from the HPE
EMESC website for further technical details regarding the configurations listed below.
Idle
LWAd
4.0 B Entry
3.9 B Base
4.4 B Perf
LpAm
28 dBA Entry
27 dBA Base
31 dBA Perf
Operating
LWAd
4.2 B Entry
4.3 B Base
4.4 B Perf
LpAm
29 dBA Entry
30 dBA Base
32 dBA Perf