HP StorageWorks SAN Switch 2/8V, 2/16V, 2/16N and 4/32 Installation Guide (AA-RVULC-TE, January 2005)

SAN Switch technical specifications104
Environmental requirements
To ensure proper operation, the switch must not be subjected to environmental conditions
beyond those for which it was tested. The ranges specified in Table 29 list the acceptable
environment for both operating and non-operating conditions.
NOTE: The -10°- 40° Celsius range applies to the ambient air temperature at the air intake
vents on the nonport side of the switch. The temperature inside the switch can be up to 7
Celsius during switch operation.
If the internal temperature range exceeds the operating ranges of the components, the LEDs,
error messages, and Fabric Watch alerts will indicate a problem. Enter the tempshow
commands to view temperature status.
Table 29 Environmental requirements
Condition Acceptable range during operation Acceptable range during
non-operation
Ambent
Temperature
-10× to +40× C (12× to 122× F) -50× to 10C (-122× to 212×
F)
Humidity 20% to 85% RH non-condensing, at
40×C, with maximum gradient of
10% per hour
10% to 85% RH noncondensing,
at 70° C
Altitude 0 to 10,000 ft (3 km) above sea level 0 to 39,370 ft (12 km) above
sea level
Shock 20 G, 6 ms duration, half sine wave 15 G, 12-18 ms duration,
trapezoid
Vibration 0.5 G, 5-500 Hz 2.0 G, 5-500 Hz
Air flow 24 cubic ft/minute None required