Installing FRUs116
Installing a new CP card
CAUTION: Do not force the installation. If the CP card does not slide in easily, ensure that it is
correctly oriented and aligned in the card guides before continuing.
To ensure proper cooling, do not route cables in front of the exhaust vent located at the top on the
port side of the chassis.
WARNING! Use the same version of Fabric OS on both CP cards. Using different versions is not
supported and might cause a malfunction. If the replacement CP card has a different version of
Fabric OS, bring both cards to the same firmware version.
Use these steps to install a new CP card in the empty card slot (#5 or #6). See Figure 31 on page
115 .
1. Open the ejector handles to approximately 45 degrees; then, orient the CP card so that the
handles are toward you and the flat metal side is on your left.
2. Align the flat metal side of the CP card inside the lower and upper card guides in the slot; then,
slide the CP card into the slot until it is firmly seated.
3. For the 4/256 SAN Director CP card, tighten the thumb screw inside each handle using the
Phillips screwdriver.
4. Turn the CP card on by sliding the ON/OFF switch in the top handle up, to cover the thumb
screw. For CP1 cards, no action is required. Go to step 5.
5. Verify that the power LED is green (wait a few seconds). If not, make sure the CP card has power
and is firmly seated and that the ejectors are in the locked position.
6. Connect the modem, serial, and Ethernet cables, as required, to the new CP card.
The new CP card assumes the IP address and host name assigned to the slot.
7. Verify the installation (see ”Verifying operation of the new CP card” next).