Brocade Fabric OS Message Reference - Supporting Fabric OS v5.3.0 (53-1000437-01, June 2007)

Fabric OS Message Reference 251
53-1000437-01
HIL-1505
30
Recommended
Action
No action is required.
Severity INFO
HIL-1505
Message <timestamp>, [HIL-1505], <sequence-number>,, WARNING, <system-name>, High
temperature (
<measured temperature> C) exceeds environmental specifications.
Probable Cause Indicates that temperatures in the system have risen above the warning threshold.
Recommended
Action
Run the fanShow command to verify all the fans are working properly.
Make sure that the area is well ventilated and that the room temperature is within operational
range of your switch. Refer to the hardware reference manual for your switch for the operational
temperature range.
Severity WARNING
HIL-1506
Message <timestamp>, [HIL-1506], <sequence-number>, FFDC, CRITICAL, <system-name>, High
temperature (
<measured temperature> C) exceeds system temperature limit.
System will shut down within 2 minutes.
Probable Cause Indicates that temperatures in the system have risen above the critical threshold.
Recommended
Action
Run the fanShow command to verify that all fans are working properly. Replace any deteriorating
fan field-replaceable units (FRUs).
Make sure that the area is well ventilated and that the room temperature is within operational
range of your switch. Refer to the hardware reference manual for your switch for the operational
temperature range.
Severity CRITICAL
HIL-1507
Message <timestamp>, [HIL-1507], <sequence-number>, FFDC, CRITICAL, <system-name>, High
temperature warning time expired. System preparing for shutdown.
Probable Cause Indicates that temperatures in the system have risen above the critical threshold.
Recommended
Action
In order to avoid causing damage to the switch, the system shuts down automatically. To help
prevent future problems, make sure that all the fans are working properly.
Make sure that the area is well ventilated and that the room temperature is within operational
range of your switch. Refer to the hardware reference manual for your switch for the operational
temperature range.
Severity CRITICAL