Brocade Fabric OS Message Reference Guide (53-1000242-01, November 2006)
9-16 Fabric OS Message Reference
Publication Number: 53-1000242-01
EM-1058
9
EM-1058
Message
Probable
Cause
The switch is automatically reset due to known resetable transient errors, such as bloom parity. error.
Recommended
Action
No action is required if the switch does not reach the reset threshold for the switch/blade. If the reset
threshold is reached on the switch/blade, the switch/blade will be faulted and should be replaced.
Severity WAR NIN G
EM-1059
Message
Probable
Cause
Indicates that a FRU inserted in the specified slot is not compatible with the switch software. The blade
will not be used.
Recommended
Action
Replace the blade. Make sure the replacement is compatible with your switch type.
Severity CRITICAL
EM-1060
Message
Probable
Cause
A blade in the system is not supported by the release on the standby CP.
Recommended
Action
Please remove all blades of this type or upgrade your standby CP. Once an appropriate action is taken,
this CP must be rebooted or haSyncStart must be run successfully. Until this is done, the system will
remain out of synchronization.
Severity WAR NIN G
<timestamp>, [EM-1058], <sequence-number>,, WARNING, <system-name>,
Switch gets reset:<Fault reason>
<timestamp>, [EM-1059], <sequence-number>, FFDC, CRITICAL, <system-
name>, Incompatible unit in <FRU Id> faulted
<timestamp>, [EM-1060], <sequence-number>,, WARNING, <system-name>,
Stopping synchronization of the system due to blade incompatibility
with software version on standby CP.