HP StorageWorks MSL4048 Tape Library firmware release notes Firmware version 6.70 (AK380-96006, December 2008)

Fixed a case where some pieces of tape media were marked as Invalid Cartridge after a
Load/Unload Timeout error.
Fixed a case where the OCP could become unresponsive after closing the mailslot.
Fixed a case where the mailslot opened unintentionally during a move operation to the front storage
slot on the right side magazine.
Added a check for the case that both the Library robotic and library controller were replaced at
the same time. If you select continue in the popup window, the Library configuration data will be
lost.
The following additional event states are logged when using the Encryption Kit:
PLK key provided
Not at BOT without read
No key got from encryption manager
Key manager not in working
Key manager not
Invalid key associated data when
Multiple keys on one
Unsupported algorithm index
Command aborted by ...
Key management error from ...
Medium not encryption capable
Fixed a case where Cleaning cartridge expired was reported for data tapes.
Fixed a case where a Robot Failure Code: 9B 37 was reported during low temperature (10 degrees
C) testing.
The network initialization sequence now begins when the Library is powered on if the Ethernet
cable is connected.
The Library now reports error code 0x80 when the bar code reader fails to complete initialization.
LT04 SAS tape drives now display port status on the RMI Drive: Status page.
Compatibility note
When using this firmware version (6.70) or future revisions with the Encryption Kit, any key server
tokens set with an odd number of characters for the PIN will not be totally backwards compatible in
Autoloaders or Libraries with code revisions 2.10, 4.00, 6.30, or 8.70 (the previous released versions).
In those cases, a token in an Autoloader or Library with 2.10, 4.00, 6.30, or 8.70 firmware revisions
will be able to accept the PIN for the token and access keys on the token, but the user will not be
able to change the PIN on the token, save the keys to a file, or restore the keys from a file until the
Autoloader or Library firmware is upgraded. Users should always upgrade to the latest version of
firmware to ensure complete compatibility.
Installation instructions
To upgrade firmware from the RMI:
1. Download current firmware using HP Library & Tape Tools or from the HP support website: http:/
/www.hp.com/support/storage.
2. Log into the RMI as the administrator user.
3. In the Support: Firmware page, browse to the location of the Library firmware file.
4