VisionPRO Product Manual

VISIONPRO
®
8000 WITH REDLINK™
68-0312—02 52
913 Dehum Fan
Control
Tstat Controls Fan
Equip Controls Fan
Tstat Controls
Fan
Both No This ISU is only displayed when ISU 900
Dehum Equipment is set to Dehumidifier.
Tstat Controls Fan: The thermostat turns on
the dehumidifier and the fan when
dehumidification is needed.
Equip Controls Fan: The thermostat turns on
the dehumidifier when dehumidification is
needed. The fan is controlled by the
equipment.
914 Run Dehumidifier
when Cool is On
Yes
No
Yes Both No This ISU is only displayed when ISU 900
Dehum Equipment is set to Dehumidifier.
Yes: Dehumidifier can run when the cooling
system is on.
No: Dehumidifier can NOT run when the
cooling system is on.
918 Dehum Away
Mode
Not Allowed
Allowed
Not Allowed Both No This ISU is NOT displayed when ISU 900
Dehum Equipment is None.
ISU 919 to 920 are only displayed when ISU
918 Dehum Away Mode is Allowed.
See “Dehumidification Away Mode” beginning
on page 85.
919 Dehum Away
Mode Fan Setting
Automatic
On
Circulate
Automatic Both No The On and Circulate settings may re-
introduce humidity into the living space.
920 Dehum Away
Mode Low Limit
Temp
70° F to 80° F
76° F Both No If the cooling system is used to control
humidity while Dehumidification Away Mode
is active, the thermostat allows the cooling
system to lower the indoor air to the Low
Limit Temperature Setting to reach the
dehumidification setting at ISU 920.
920 Dehum Away
mode Temp
Setting
70° F to 99° F
85° F Both No The temperature maintained while
Dehumidification Away Mode is active and the
desired humidity level is satisfied.
920 Dehum Away
mode Dehum
Setting
40% to 70% (in 5% increments)
65% Both No The desired humidity level while
Dehumidification Away Mode is active.
921 Dehumidifier Filter
Reminder
Off
30, 60, Calendar Days
3 to 12 Calendar Months (in 1
month increments)
Off Both No
1000 Ventilation Type
None
ERV / HRV
Passive (Fan Only)
Fresh Air Damper
None Both No None: The thermostat does not control
ventilation.
ERV/HRV: The thermostat controls an Energy
Recovery Ventilator or Heat Recovery
Ventilator for ventilation.
Passive (Fan Only): The thermostat turns on
the fan for ventilation.
Fresh Air Damper: The thermostat turns on
the fan and opens a fresh air damper for
ventilation.
Table 2. Installer Setup (ISU) Table. (Continued)
ISU
Number
Installer Setup
Name Settings Default
Residential,
Commercial
or Both
Requires
EIM Notes