Thermostat User's Manual
WEBVISION™
169 95-7769—01
Holiday nvoData2 holiday EnumPoint
Next State nvoData2 schedNextState EnumPoint
Occupancy Sensor nvoData2 occSensor EnumPoint
Outdoor Temperature nvoData1 oDTemp NumericPoint
Percent Cool Command nvoData1 percentCmdCool NumericPoint
Percent Heat Command nvoData1 percentCmdHeat NumericPoint
Relay Heat 2 nvoData2 relayHeat2 EnumPoint
Remote Setpoint Offset nvoData2 remoteStPtOffset NumericPoint
Scheduled State nvoData2 scheduledState EnumPoint
Space Humidity nvoData1 spaceHumidity NumericPoint
Space Temperature nvoData1 spaceTemp NumericPoint
Stages Active nvoData2 stagesActive NumericPoint
SubBase Type nvoData1 subBaseType EnumPoint
System Mode nvoData1 sysMode EnumPoint
Temporary Setpoint nvoData2 temporarySetPt NumericPoint
Terminal Load nvoData1 terminalLoad NumericPoint
Time To Next State nvoData2 scheduledTuncos NumericPoint
Total Error nvoData2 totalError NumericPoint
nviTimeSet year Numeric Writable
nviTimeSet month Numeric Writable
nviTimeSet day Numeric Writable
nviTimeSet hour Numeric Writable
nviTimeSet minute Numeric Writable
nviTimeSet second Numeric Writable
Table 92. T7350 Point Details. (Continued)
Point Name Network Variable Field Point Type
Table 93. T7350 Application of Points.
Point Name Graphics Alarms Trends Commandable Internal Use Valid Values
Occupied Cool (Setpoint) X Units=ºC
Precision=2
Min=7.2
Max=37.2
Standby Cool (Setpoint) X Units=ºC
Precision=2
Min=7.2
Max=37.2
Unoccupied Cool (Setpoint) X Units=ºC
Precision=2
Min=7.2
Max=37.2
Occupied Heat (Setpoint) X Units=ºC
Precision=2
Min=4.4
Max=32.2
Standby Heat (Setpoint) X Units=ºC
Precision=2
Min=4.4
Max=32.2