Thermostat User's Manual
WEBVISION™
119 95-7769—01
Discharge Air Temperature X X X Units=ºF
Precision=1
Min=-256.0
Max=256.0
Discharge Setpoint X X X Units=ºF
Precision=1
Min=-256.0
Max=256.0
Economizer Enable X X X Default
Off
Low
Medium
High
On
Economizer Float Synch X X X Off or On
Economizer Position X X X Units=%
Precision=0
Min=-128.0
Max=127.0
Effective Occupancy X X X Default
Occupied
Unoccupied
Bypass
Standby
Effective Setpoint X X X Units=ºC
Precision=1
Min=-273.2
Max=327.7
Fan Status X X X Off or On
Filter Air Pressure X X X Units=in/wc
Precision=1
Min=-32.0
Max=32.0
Free1 Out X X X Off or On
Free2 Out X X X Off or On
Heat Percent X X X Units=%
Precision=1
Min=-163.8
Max=163.8
Heat Position X X X Units=%
Precision=0
Min=-128.0
Max=127.0
Heat Stages On X X X Units=null
Precision=0
Min=0.0
Max=7.0
Indoor Air Quality Override X X X False
True
Manual Override X X X Default
Occupied
Unoccupied
Bypass
Standby
Table 77. CVAHU Application of Points. (Continued)
Point Name Graphics Alarms Trends Commandable Internal Use Valid Values