Thermostat User's Manual
WEBVISION™
111 95-7769—01
DLC Shed X X X Restored or Shed
Economizer Output X X X Units=%
Precision=1
Min=-163.8
Max=163.8
Effective Occupancy X X X Default
Occupied
Unoccupied
Bypass
Standby
Effective Sensor Occupancy X X X Default
Occupied
Unoccupied
Bypass
Standby
Effective Window Open X X X Closed or Open
External Active X X X Inactive or Active
Fan Feedback X X X Failure or Running
Fan Output X X X Units=%
Precision=1
Min=-163.8
Max=163.8
Fan Stages Active X X X Fan Off
Fan Speed 1
Fan Speed 2
Fan Speed 3
Fan Auto
Fan Default
HW Override X X X Default
Occupied
Unoccupied
Bypass
Standby
HW Window Open X X X Closed or Open
Humidity X X X Units=%RH
Precision=1
Min=-163.8
Max=163.8
Manual Occupancy X X X Default
Occupied
Unoccupied
Bypass
Standby
Table 75. CHC Application of Points. (Continued)
Point Name Graphics Alarms Trends Commandable Internal Use Valid Values