Install Instructions

MVN 3Nm (27 lb-in.) Control Ball Valve Actuator
62-2025EFS—03 6
Fig. 15. MS7505 with Proportioning controllers operating
multiple actuators (Modulating mode setting).
Fig. 16. MVN613 or MVN643 with Floating Control.
Fig. 17. MVN613 or MVN643 with 2-Position Control.
Fig. 18. MVN643 with Two Position SPST Control.
Fig. 19. MVN713 with 4-20mA Control.
ACTUATOR
0/2 TO 10 VDC
PROPORTIONING
CONTROLLER
1
2
3
2
LINE VOLTAGE POWER SUPPLY.
PROVIDE DISCONNECT MEANS AND
OVERLOAD PROTECTION AS REQUIRED.
24 VDC SUPPLY ACCEPTABLE.
SET SWITCH TO MODULATING.
V
OR +
OR N/A
FEEDBACK
5
4
3
1
2
M34978
2-10 VDC
10-2 VDC
0-10 VDC
10-0 VDC
Fltg, fwd
Fltg, rev
3
ACTUATOR
V
OR +
OR N/A
FEEDBACK
5
4
3
1
2
2-10 VDC
10-2 VDC
0-10 VDC
10-0 VDC
Fltg, fwd
Fltg, rev
3
24 VAC
1
24 VAC
1
2
24 VAC
1
HOT
COM
+
FLOATING ACTUATOR
24 VAC
1
POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD
PROTECTION AS REQUIRED.
USE CLASS II 24V TRANSFORMER FOR MVN643.
FLOATING
CONTROLLER
M33137C
2
3
4
1
BLACK
WHITE
BROWN
2
2
POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD
PROTECTION AS REQUIRED.
USE CLASS II 24V TRANSFORMER FOR MVN643.
2
FLOATING ACTUATOR
24 VAC
1
FLOATING
CONTROLLER
2
3
4
1
M33138C
BLACK
WHITE
BROWN
2
M33557B
FLOATING ACTUATOR
1
POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD
PROTECTION AS REQUIRED.
USE CLASS II 24V TRANSFORMER.
2
3
4
1
24 VAC
BLACK
BROWN
WHITE
SPST
2
2
PROPORTIONAL ACTUATOR
1
POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD
PROTECTION AS REQUIRED.
USE CLASS II 24V TRANSFORMER.
4-20mA
CONTROLLER
M33141B
1
2
3
+
+
DIP SWITCH POSITION
1 2 MODE
OFF OFF 2-10V
OFF ON 0-10V
ON OFF 10-2V
ON ON 10-0V
PROPORTIONAL/MODULATING: 4-20mA CONTROLLER OUTPUT WITH
500Ω SERIES RESISTOR
TO OTHER
ACTUATORS
500 OHMS,
1/2 W
MINIMUM
24 VAC
2
RED
BLACK
WHITE
1
2