User Guide
V48A,F,J; V88A,J DIAPHRAGM GAS VALVES
60-2080—9 2
ORDERING INFORMATION
When purchasing replacement and modernization products from your TRADELINE® wholesaler or distributor, refer to the
TRADELINE® Catalog or price sheets for complete ordering number.
If you have additional questions, need further information, or would like to comment on our products or services, please write or
phone:
1. Your local Honeywell Automation and Control Products Sales Office (check white pages of your phone directory).
2. Honeywell Customer Care
1885 Douglas Drive North
Minneapolis, Minnesota 55422-4386
In Canada—Honeywell Limited/Honeywell Limitée, 35 Dynamic Drive, Scarborough, Ontario M1V 4Z9.
International Sales and Service Offices in all principal cities of the world. Manufacturing in Australia, Canada, Finland, France,
Germany, Japan, Mexico, Netherlands, Spain, Taiwan, United Kingdom, U.S.A.
SPECIFICATIONS
Models:
V48A (120 Vac) or V88A (24 Vac) solenoid operated
diaphragm valves for 1/2 or 1 psi (3.4 or 6.9 kPa) maximum
operating pressure.
V48F (120 Vac) solenoid operated diaphragm valve for 5 psi
(34.5 kPa) maximum operating pressure.
V48J (120 Vac) or V88J (24 Vac) solenoid operated
diaphragm valves for 1 psi (6.9 kPa) operating pressure
and 150°F maximum ambient temperature.
Type of Gas: Suitable for liquefied petroleum (LP), natural,
manufactured, and sulfur-bearing gases.
Valve Capacity: See table in Fig. 2.
Valve Pattern: Straight-through, non-offset.
Valve Body Material: Die-cast aluminum.
Pilot Tapping (see Table 1 for thread type):
3/4 through 1-1/2 inch valves: 1/8-27 NPT or 1/8-28 BSP.PI.
2 through 3 inch valves: 1/4-18 NPT.
Bleed Tapping (see Table 2 for thread type): 1/8-27 NPT or
1/8-28 BSP.PI.
Valve Opening Time:
Five seconds maximum at 2 oz/in.
2
(0.86 kPa) pressure.
Adjustable bleed valve assembly or fixed bleed orifices
available for longer opening time (NPT threads only; see
Accessories).
Valve Closing Time (on power failure; measured at
2 oz/in.
2
[0.86 kPa] pressure): 2 seconds maximum.
Maximum Operating Pressure: See Table 2.
Power Consumption (maximum): 9 watts or 15 VA.
Ambient Temperature Rating:
V48A,F and V88A: 32°F to 125°F (0°C to 52°C).
V48J and V88J: 32°F to 150°F (0°C to 66°C).
Maximum Fluid Temperature:
V48A,F; V88A: 125°F (52°C).
V48J; V88J: 150°F (66°C).
Thermostat Heat Anticipator Setting: For 60 Hz V88, set at
0.6A.
Dimensions: See Fig. 1.
Weight: See Table 1.
Table 1. Valve Weight.
Approvals: (60 Hz models only):
Underwriters Laboratories Inc. Listed: File No. MH1639;
Guide No. YIOZ.
CSA 158158-2500005576 (Z21.21-CSA 6.5).
NOTE: All models rated at 50 Hz and all models with BSP.PI
threads are not CSA Design Certified.
Optional Feature: Valve position indicator is available on
1-1/4 in. V48A2227 and 2 in. V48F1103.
Replacement Coil Assemblies:
a
116930: 24V, 60 Hz V88A
116931: 120V, 60 Hz V48A.
116932: 220V, 50 Hz V48A
116932: 240V, 60 Hz V48A
118888: 24V, 60 Hz V88J
139937: 120V, 60 Hz V48J
a
These V48/V88 bonnet assemblies and solenoid operators
are not compatible with old style valve bodies.
Pipe Size (in.) lb kg
3/4 2-1/2 1.13
1 3 1.36
1-1/4 3-1/2 1.59
1-1/2 4 1.81
2 9 4.08
2-1/2 8-1/2 3.86
3 9-1/2 4.31