Submittal Sheet

M6410A,M7410F,M6435A,M7435F ACTUATORS V5852A, V5853A, V5862A, V5863A VALVES
5 62-0100—9
CAUTION
Electrical Shock or Equipment Damage Hazard.
Can shock individuals or short equipment
circuitry.
Disconnect power supply before installation.
CAUTION
Sweat Valve Damage Hazard.
Soldering the valve with the cartridge in place can
damage the device.
Prior to attaching valve to piping, remove cartridge
from potential exposure to heat.
IMPORTANT
Before installing the valve and actuator, use the
protective cover/manual handle to ensure the valve
stem operates freely. Impaired stem operation can
indicate a bent stem (due to rough handling). This
condition can require replacing the valve.
When installing valves, make sure the flow direction
is correct by checking the arrow on the valve body.
Mount the valve only with the stem pointing upward.
Leave the protective cover in place until ready to
attach the actuator.
Location
Select a location where the valve and actuator are accessible.
IMPORTANT
Mount all valve types in return flow. When delta p-
values exceed 8.70 psi (60 kPa), noise can develop.
Mounting
Valve
The valve body should be completely installed in the pipe line
before the actuator is installed.
IMPORTANT
The insert is packed separately from the V5852,
V5853 Sweat Valve. The valve must be installed and
soldered before the insert is installed in the valve.
Torque the insert between 27 and 44 in.-lb.
1. Verify pipe size and flow direction for the valve being
used.
2. Position the valve so that the actuator can be easily
installed.
3. Install the valve using the applicable tools and supplies
(wrenches, solder, flux, torch or soldering iron). Follow
standard practices.
Actuator
No tools are required to install the M6410A or M7410F on a
valve because they are threaded onto the valve by hand. Do
not overtighten by using a wrench on the connection, because
this can damage the valve or actuator.
To mount the M6410A or M7410F Actuator, refer to Fig. 4
through 6. Fig. 5 shows the valve position indicator.
Fig. 4. Removing protective cover from valve.
Fig. 5. Valve position indicator (M6410 shown).
Fig. 6. Mounting actuator to valve (M6410 shown).
1. Remove the protective cover from the valve (Fig. 4).
2. Make sure the actuator is in the (factory-supplied)
OPEN position.
3. Screw the actuator connector onto the body of the valve
(Fig. 6).
Wiring
Connect the M6410A, M6435A Actuators to the controller
using the controller wiring diagram. See Fig. 8 for a typical
T6984F hookup. For Excel 10
®
hookup see Fig. 11.
M8228A
M8227
A
M8229B