Product Overview
PRODUCT DATA
66-2039-02
V5097A-E
Industrial Gas Valves
APPLICATION
The V5097A-E Gas Valves are used with the V4055, V4062
and V9055 Fluid Power Actuators to control gas flow to
commercial and industrial burners.
NOTICE: Per Industry Standards, the actuator is required a
conduit seal or a cable type that is sealed be installed in a
device that can result in a flammable liquid flow through a
conduit or cable to an electrical ignition source in the event of
a seal leakage or diaphragm failure.
FEATURES
• Used with natural or liquefied petroleum (LP) gases.
• V5097 normally closed valves are rated for final shutoff
service (safety shutoff).
• V5097A,C,D,E Valves are for On-Off service.
• V5097B Valve has a characterized guide and in
combination with the V4055, V4062 and V9055 Fluid
Power Actuators, provides slow-opening, HI-LO-OFF, and
modulating functions, respectively.
•V
5097C,E Valves have a double seal and are used
with V4055D,E Fluid Power Actuators to provide
proof-of-closure switch and valve seal overtravel
interlock.
• V5097D,E Valves are for high pressure applications (see
Table 1).
• Two valve body types (small and large) applicable to seven
pipe sizes:
— Small body type for 3/4 in. (19 mm), 1 in. (25 mm), 1-1/
4 in. (32 mm), 1-1/2 in. (38 mm) and 2 in. (51 mm)
pipes.
— Large body type for 2 in., 2-1/2 in. and 3 in. pipes.
• Seven pipe adapter sizes (3/4 in. to 3 in.) have NPT or
BSP-PL threaded connections.
• V5097 version provides three 1/4 in. upstream and two 1/4
in. downstream taps and plugs. European Community
(CE) version provides an additional downstream tap and
plug.
• Valve body rating of 75 psi (517.1 kPa); body passes
Underwriters Laboratories Inc. burst test.
• Yellow SHUT indicator attached to valve stem indicates
valve closed position.
• Unpainted die-cast aluminum body.
SPECIFICATIONS
IMPORTANT:
The specifications given in this publication do not
include normal manufacturing tolerances; therefore,
an individual unit may not exactly match the listed
specifications. Also, this product is tested and cali-
brated under closely controlled conditions, and some
minor differences in performance can be expected if
those conditions are changed.
Models (See Table 1):
Type of Gas: Natural or liquefied petroleum (LP) only.
Pipe Size: 3/4 in., 1 in., 1-1/4 in., 1-1/2 in., 2 in., 2-1/2 in., 3 in.
Pipe Threads: NPT or BSP-PL threads (equivalent to ISO R7
and DIN 2999). 3/4 in. to 3 in. pipe adapters available.
Pressure Ratings: See Table 2.