V4043A,B,E,J; V4044A,B; V8043A,B,E,F,J; V8044A,B,E Motorized Valves PRODUCT DATA FEATURES • The V4043 and V8043 provide 2-position, straightthrough control of water. • The V4044 and V8044 provide 2-position diverting control of water. V4043, V4044, V8043, V8044 Replacement Powerhead • Compact construction for easy installation. V4043, V8043 • Manual opener for valve operation on power failure. Valve returns to automatic position when power is restored.
V4043A,B,E,J; V4044A,B; V8043A,B,E,F,J; V8044A,B,E MOTORIZED VALVES Electrical Ratings (See Table 1 for Voltage of Specific Models): SPECIFICATIONS TRADELINE® Models TRADELINE® models are selected and packaged to provide ease of stocking, ease of handling, and maximum replacement value. TRADELINE® model specifications are the same as those of standard models except as noted below. Voltage Amperes 24 0.320 a Voltage Amperes 220 0.042 100 0.087 240 0.040 120 0.080 277 0.037 208 0.
V4043A,B,E,J; V4044A,B; V8043A,B,E,F,J; V8044A,B,E MOTORIZED VALVES 6 V043, V8043 SWEAT COPPER CONNECTION MODELS V4044, V8044 SWEAT COPPER CONNECTION MODELS 5 3-1/2 (89) 1 7/8 DIA.
V4043A,B,E,J; V4044A,B; V8043A,B,E,F,J; V8044A,B,E MOTORIZED VALVES Table 1. Powerhead and Valve Body Specifications Flow Capacity Rating Model V4043A V4043B Control Circuit V4044A kV Type 120V, 60 Hz 3.5 3.0 120V, 60 Hz 8.0 7.0 Sweat 3/4 120V, 60 Hz 8.0 7.0 Sweat 1 120V, 60 Hz 3.5 3.0 NPT 1/2 120V, 60 Hz 3.5 3.0 NPT 3/4 120V, 60 Hz 10.0 8.6 NPT 1 208V, 60 Hz 3.5 3.0 Flare 1/2 220V, 50 Hz 3.5 3.0 Flare 1/2 240V, 50 or 60 Hz 3.5 3.
V4043A,B,E,J; V4044A,B; V8043A,B,E,F,J; V8044A,B,E MOTORIZED VALVES Flow Capacity Rating Model V8043A V8043B V8043E V8043F V8043J V8044A Pipe Connections Control Circuit Cv kV 24V, 60 Hz 3.5 3.0 24V, 60 Hz 3.5 3.0 NPT 1/2 24V, 60 Hz 3.5 3.0 Sweat 3/4 24V, 60 Hz 8.0 7.0 36 in. (914 mm) leadwires, Sweat 1/2 in. conduit opening. 3/4 24V, 60 Hz 3.5 3.0 18 in. (457 mm) leadwires, Sweat 1/2 in. conduit opening. 1 Wire Hookup Type 18 in. (457 mm) leadwires, Sweat or 1/2 in.
V4043A,B,E,J; V4044A,B; V8043A,B,E,F,J; V8044A,B,E MOTORIZED VALVES Flow Capacity Rating Model Control Circuit Cv Pipe Connections kV Wire Hookup Type Size (in.) Valve Body De-energized Position V8044B 24V, 60 Hz b 4.0 3.4 18 in. (457 mm) leadwires, Sweat 1/2 in. conduit opening. 1/2 2-position Port A Normally diverting Closed V8044E 24V, 60 Hz 4.0 3.4 18 in. (457 mm) leadwires and end switch, 1/2 in. conduit opening.
V4043A,B,E,J; V4044A,B; V8043A,B,E,F,J; V8044A,B,E MOTORIZED VALVES Table 2. Replacement Powerheads. Valve Model Number V4043A V4043B Electrical Connection on Which Side of Manual Lever Voltage (Vac) and Frequency (Hz) Current Draw (A) 40003916-022 Same 220/50, 240/60 0.04 40003916-023 Same 240, 50 0.04 40003916-024 Same 120, 60 0.08 Part Number Type of Electrical Connection Motor 18 in (457 mm) leads (conduit opening) Class F; plated 40003916-030 Same 240, 60 0.
V4043A,B,E,J; V4044A,B; V8043A,B,E,F,J; V8044A,B,E MOTORIZED VALVES MAXIMUM AMBIENT TEMPERATURE LINE 210 (99) 200 (93) 190 (88) 180 (82) MAXIMUM FLUID TEMPERATURE LINE AMBIENT TEMPERATURE 170 (77) 160 (71) 150 (66) EXAMPLE: 150°F (66°C) IS THE AMBIENT TEMPERATURE AT THE VALVE, 235°F (113°C) IS MAXIMUM FLUID TEMPERATURE.
V4043A,B,E,J; V4044A,B; V8043A,B,E,F,J; V8044A,B,E MOTORIZED VALVES PRESSURE DROP, EQUIVALENT FEET OF PIPE (EQUIVALENT METERS OF PIPE) 90 100 (27) (30) 120 (37) (1/2 IN. PIPE) PRESSURE DROP, EQUIVALENT FEET OF PIPE (EQUIVALENT METERS OF PIPE) 750 (229 ) 500 600 700 (152) (183) (213) 140 (43) (3/4 IN. PIPE) (3/4 IN. PIPE) 30 (207) 8.0 (2.4) 9.0 (2.7) 10 (3) 45 (13.7) 11 (3.4) 60 (18) 12 (3.6) 13 (4) 12.5 (3.8) 80 (24.4) 70 (21.3) 65 (20) (1/2 IN.
V4043A,B,E,J; V4044A,B; V8043A,B,E,F,J; V8044A,B,E MOTORIZED VALVES INSTALLATION PRESSURE DROP, EQUIVALENT FEET OF PIPE (EQUIVALENT METERS OF PIPE) 10 13 15 17 19 20 21 22 23 24 25 (3) (4) (4.6) (5.2) (5.8) (6) (6.4) (6.7) (7) (7.3) (7.6) (3/4 IN. PIPE) 2.0 (0.6) 3.0 (0.9) 3.5 (1) When Installing this Product… (1/2 IN. PIPE) 1. Read these instructions carefully. Failure to follow them could damage the product or cause a hazardous condition. 2.
V4043A,B,E,J; V4044A,B; V8043A,B,E,F,J; V8044A,B,E MOTORIZED VALVES 쐏 Remove the old powerhead from the valve body (Fig. 10): a. Place the manual opening lever (normally closed models only) on the old powerhead in the MAN. OPEN position (see Fig. 10A). b. Remove the cover (Fig. 10B). c. With the cover off, remove the four screws securing the powerhead to the valve body. d. Lift the powerhead off the valve body (Fig. 10C). e. Remove the O-ring from the top of the valve body.
V4043A,B,E,J; V4044A,B; V8043A,B,E,F,J; V8044A,B,E MOTORIZED VALVES A C MAN OPEN AUTO MANUAL OPENING LEVER 6 51 3F 10 V804 0 CY /6 0 5 24V 60 CY MP @ .32 A DA CANA IN E MAD A B A B COVER RETAINING SCREW 6 51 3F 10 V804 0 CY /6 0 5 24V 60 CY MP @ .32 A DA CANA IN E MAD A B M10174 Fig. 10. Remove old powerhead from systems using old style valve bodies.
V4043A,B,E,J; V4044A,B; V8043A,B,E,F,J; V8044A,B,E MOTORIZED VALVES HEX-NUT SCREW WITH DOMED HEADS (2) Systems with New Style Valve Bodies (Series 6) HEX-NUT SCREWS WITH RECESSED THREADS AND SHOULDER SHANK (2) IMPORTANT On a new style valve body or a valve body that was converted to accept the new powerhead, it is not necessary to drain the system if the valve body remains in the pipeline. 쐃 Disconnect the power supply before connecting the wiring to prevent electrical shock or equipment damage.
V4043A,B,E,J; V4044A,B; V8043A,B,E,F,J; V8044A,B,E MOTORIZED VALVES A THERMOSTAT (TYPICALLY T87F) TO LINE TO CIRCULATOR OR ANOTHER VALVE YELLOW LEADS RED LEADS MOTOR M AN O PEN AUXILIARY SWITCH AUTO MANUAL OPENING LEVER B A M5953 B Fig. 14. Typical wiring for V8043E, V8044E. R THERMOSTAT (TYPICALLY T87F) TO CIRCULATOR OR ANOTHER VALVE END SWITCH COVER RETAINING SCREW TH TR TH TR 1 L1 (HOT) L2 24V TRANSFORMER 6 36 3F 10 V804 CY 0/60 24V 5 60 CY MP @ .
V4043A,B,E,J; V4044A,B; V8043A,B,E,F,J; V8044A,B,E MOTORIZED VALVES T822 T822 V4044, V8044 VALVE OPERATOR T822 HEATING COOLING THERMOSTAT RED 1 L1 (HOT) L2 BLUE 1 2 2 2 V8043A V8043A V8043A MOTOR 1 AQUASTAT® CHANGEOVER CONTROL SWITCHES TO HEATING (RED) AT FLUID TEMPERATURE OF 85°F (29°C) MAX TO COOLING (BLUE) AT FLUID TEMPERATURE OF 60°F (18°C) MIN. M10171 1 POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.
V4043A,B,E,J; V4044A,B; V8043A,B,E,F,J; V8044A,B,E MOTORIZED VALVES ZONE 1 ZONE 2 ZONE 3 T87F T87F T87F V8043F V8043F V8043F END SWITCH END SWITCH END SWITCH TH-TR TH TR TH-TR TH TR TH-TR TH TR TV T Z 2 L1 (HOT) 1 L8124G C1 ADD JUMPER TO EACH VALVE 120 V POWER SUPPLY L2 B1 B2 C2 TO CIRCULATOR TO BURNER CIRCUIT M5954 Fig. 20. Typical 3-zone system. Use an AT87A Transformer to power up to five more zone valves.
V4043A,B,E,J; V4044A,B; V8043A,B,E,F,J; V8044A,B,E MOTORIZED VALVES ZONE 2 ZONE 1 T87F T87F V8043F T87F V8043F END SWITCH TH-TR TH ZONE 4 ZONE 3 TH-TR TH TR ZONE 5 T87F T87F V8043F END SWITCH END SWITCH TH-TR TH TR AT87A TRANSFORMER V8043E V8043E YELLOW YELLOW YELLOW YELLOW RED RED RED RED TR L1 (HOT) L2 1 1 TO BURNER AND / OR CIRCULATOR CIRCUIT POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.
V4043A,B,E,J; V4044A,B; V8043A,B,E,F,J; V8044A,B,E MOTORIZED VALVES FLAIR VALVE DOLE VALVE A A L1 (HOT) L1 (HOT) C B D 1 L2 TO TERMINALS T, T ON BURNER RELAY F 2 L2 4 E 3 1 2 3 1 B 1 4 THERMOSTAT 5 E F D C POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED. 1 TO TERMINALS T, T ON BURNER RELAY M5977 THERMOSTAT 1 Fig. 26. Existing Dole System. (Wires are identified with letters to correspond with wires in Fig. 27 and 28.) M5978 Fig. 29.
V4043A,B,E,J; V4044A,B; V8043A,B,E,F,J; V8044A,B,E MOTORIZED VALVES WHITE-RODGERS 1311 OR 1321 VALVE WATER VALVE THERMOSTAT V8043F TO AUXILIARY CIRCUIT END SWITCH TO AUXILIARY CIRCUITS 2 5 6 4 1 6 3 4 2 1 L1 (HOT) 5 1 L2 L1 (HOT) L2 1 POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED. 6 5 M5711 4 3 Fig. 32. Existing White-Rodgers System.
V4043A,B,E,J; V4044A,B; V8043A,B,E,F,J; V8044A,B,E MOTORIZED VALVES open valve. OPERATION AND CHECKOUT NOTE: Inlet Port is stamped A and Outlet Port is stamped B on the valve body. CAUTION Fig. 36. V8043 operation for normally closed valve. On 24V systems, never jumper the valve coil terminals even temporarily. This can burn out the heat anticipator in the thermostat.