Submittal Sheet

2
TP973A AND B ROOM THERMOSTATS
77-9826
Honeywell Europe S.A.
3 Avenue du Bourget
B-1140 Brussels Belgium
Honeywell Asia Pacific Inc.
Room 3213-3225
Sun Hung Kai Centre
No. 30 Harbour Road
Wanchai
Hong Kong
Home and Building Control
Honeywell Limited-Honeywell Limitée
155 Gordon Baker Road
North York, Ontario
M2H 2C9
Honeywell Latin American Division
Miami Lakes Headquarters
14505 Commerce Way Suite 500
Miami Lakes FL 33016
Helping You Control Your World
®
77-9826-1 Rev. 8-96
Home and Building Control
Honeywell Inc.
Honeywell Plaza
P.O. Box 524
Minneapolis MN 55408-0524
Printed in U.S.A. on recycled paper
containing at least 10% post-consumer paper fibers
SPECIFICATIONS
Models:
TP973A Thermostat (direct acting)
TP973B Thermostat (reverse acting)
Setpoint Range:
60 to 90F (15 to 30C)
Straight-line scale setpoint indicator
Sensing Element:
Bimetal
Thermometer:
60 to 90F (15 to 30C)
Throttling Range:
Adjustable 2 to 10 degrees F (1 to 6 degrees C)
Supply Air Pressure:
18 psi (124 kPa)
Maximum Safe Air Pressure:
25 psi (172 kPa)
Air Consumption:
0.011 scfm (5.2 ml/s)
Air Filter:
Replaceable cartridge type
Maximum Operating Temperature:
100F (38C)
Maximum Storage Temperature:
150F (66C)
Setpoint Adjustment:
External knob
Knob can be covered or left accessible as required
Stops available as an accessory
Branchline Indication:
Self-sealing gage tap accessible under cover
Mounting:
Wall mounted on plug-in backplate in horizontal or
vertical orientation
Dimensions:
3-1/4 in. (83 mm) wide x 2 in. (51 mm) high x 1-5/8 in.
(42 mm) deep
Cover and Accessories:
Order separately (see HP970 and TP970 Series Standard
Covers and Accessories Specification Data 77-1003)
TP973 Setpoint Stop Kit — 14004908-001
14004908-001 Setpoint Stops for TP973 (bag of 10 for
5 thermostats)
C7868
Fittings:
Order separately (see HP970-72 and TP970-74 Pneumatic
Sensors, Humidistats, and Thermostats Installation
Instructions 95-5597)