Thermostat User Manual
5-1
SECTION 5
Testing the 4500 With the 4286
••••••••••••••••••••••••••••••••••••••••••
In This Section
♦
General
♦
Step-by-Step Testing Procedure
♦
Setting the Premises thermostat
♦
Setting the 4500 Thermostat
♦
Menu Selections
••••••••••••••••••••••••••••••••••••••••••
General
Once the 4500 has been installed, and the 4286 programmed, the system may
be tested with the following procedure.
Step-by-Step Testing Procedure
Perform the steps that follow in order:
1. Bypass all interior zones and any others that may cause an alarm while
the security system is armed in the away state.
2. Arm the security system to the ARMED AWAY state. You are about to
perform a test of the 4500 thermostat set-back operation.
3. If the 4500 will control a heating system, set the 4500 front panel slide
switches to ACTIVE and HEAT. Set the premises thermostat into its
heat mode as well. If only air conditioning will be controlled, skip to
step 6.
4. Perform the following test: Set the set points according to the steps
described in “Setting the Premises and 4500 Thermostat” sections that
follow. Set the premises thermostat 10 degrees higher than room
temperature. Set the 4500 set point to a temperature 5 degrees lower
than the room temperature. The heat should turn off within one minute.
Set the 4500 set point to a temperature 5 degrees higher than room
temperature. The heat should turn on within one minute.