Specifications

VisionPRO
®
8000 with RedLINK
Job Name
Engineer
Mechanical Contractor
Contractor’s P.O. No.
Representative
Notes
Model(s) Qty.
TH8321R1001
TH8320R1003
TH8110R1008
THM5421R1021
Approval
Service
Tag No.
SUBMITTAL SHEET
APPLICATION
RedLINK VisionPRO is a 7-Day programmable thermostat with auto
changeover that is designed for single stage and multistage control
of conventional and heat pump equipment such as rooftop units and
split systems in residential and commercial applications. RedLINK
VisionPRO can be used with or without an equipment interface module.
The thermostat controls up to 3 heat / 4 cool conventional systems
and up to 4 heat / 2 cool heat pump systems. The thermostat controls
humidication, dehumidication, ventilation, an economizer and a
lighting panel. Universal sensor inputs are used with remote indoor air
temperature sensor(s), an outdoor air temperature sensor, a discharge
air temperature sensor, a return air temperature sensor, an occupancy
sensor for remote setback and dry contact devices for displaying alerts.
The thermostat is equipped with a touchscreen display with a 2 line
message center.
Provides a microSD card port to upload Dealer Information, Custom
Reminders, Custom Event Schedules, Holiday Schedule and
Software Updates and to download Data Logs.
Provides remote access to the thermostat when used with the
RedLINK internet gateway.
Provides control using optional remote temperature and humidity
sensors.
Thermostat integrates with the Niagara-AX framework.
SPECIFICATIONS
Terminal Designations:
Equipment Interface Module: R, RC, RH, C, W-O/B, W2-AUX 1, W3-
AUX 2, Y, Y2, G, A-L/A, U1 U1, U2 U2, U3 U3, S1 S1, S2 S2, S3
S3, S4 S4, A, B, C, D
TH8321 Thermostat: R, RC, C, W-O/B, W2-AUX/E, Y, Y2, G, A-L/A, K,
U1 U1, S1 S1
TH8320 Thermostat: R, RC, C, W-O/B, W2-AUX/E, Y, Y2, G, A-L/A, K,
S1 S1
TH8110 Thermostat: R, RC, C, W-O/B, Y, G, K, S1 S1
Electrical Ratings (for VisionPRO and Equipment Interface
Module):
Terminal Voltage
(50/60 Hz)
Max. Current
Rating
W - O/B 18 to 30 VAC
and 750 mVDC
1.00A
Y (cooling) 18 to 30 VAC 1.00A
G (fan) 18 to 30 VAC 0.50A
W2 - Aux 1 (heating) 18 to 30 VAC 0.60A
W3 - Aux 2 (heating) 18 to 30 VAC 0.60A
Y2 (cooling) 18 to 30 VAC 0.60A
A-L/A (Output) 18 to 30 VAC 1.00A
(U1, U1), (U2, U2), (U3, U3) 30 VAC max. 0.50A
Power Consumption of TH8321/TH8320/TH8110 Thermostat:
Backlight on: 1.44 VA
Backlight off: 1.32 VA
Power Consumption of Equipment Interface Module: 2.0 VA
RedLINK Communication:
Frequency: 900 Mhz frequency range
Re-Sync Time: RedLINK devices re-establish communication
within 6 minutes after AC power resumes.
Temperature Setting Range:
Heating: 40 to 90 °F (4.5 to 32 °C)
Cooling: 50 to 99 °F (10 to 37 °C)
Temperature Sensor Accuracy:
± 1.5 °F at 70 °F (0.75 °C at 21.0 °C)
Humidication Setting Range: 10% to 60% RH
Dehumidication Setting Range: 40% to 80% RH
Humidity Display Range: 0% to 99%
Humidity Sensor Accuracy:
± 5% RH from 30% to 50% RH at 75 °F (24 °C)
Cool Indication:
Displays “Cool On” when the thermostat turns the cooling on.
33-00016-01

Summary of content (2 pages)