Lyric™ T6 Pro Wi-Fi Programmable Thermostat Professional Install Guide Package Includes: • Lyric T6 PRO Wi-Fi Thermostat • UWP Mounting System • Honeywell Standard Installation Adapter (J-box adapter) • Honeywell Decorative Cover Plate – Small; size 4-49/64 in = 121mm. *TH6320WF2003 depicted. Other models may vary.
UWP Mounting System installation 1. Open package to find the UWP. See Figure 1. 1 2 2. Position the UWP on the wall. Level and mark hole positions. See Figure 2. Drill holes at marked positions, and then lightly tap supplied wall anchors into wall using a hammer. ‒‒ Drill 7/32” holes for drywall. 3 4 1/4” 8” to 3/ 3. Pull the door open and insert wires through wiring hole of the UWP. See Figure 3. 4. Place the UWP over the wall anchors. Insert and tighten mounting screws supplied with the UWP.
Wiring UWP Push down on the tabs to put the wires into the inner holes of their corresponding terminals on the UWP (one wire per terminal) until they are firmly in place. Gently tug on the wires to verify they are secure. If you need to release the wires again, push down the terminal tabs on the sides of the UWP. This wiring is just an example, yours may vary.
Setting Slider Tabs Set R Slider Tab, see Figure 9. • Use built-in jumper (R Slider Tab) to differentiate between one or two transformer systems. 9 • If there is only one R wire, and it is connected to the R, Rc, or RH terminal on the old thermostat, set the slider to the up position (1 wire). • If there is one wire connected to the R terminal and one wire connected to the Rc terminal, set the slider to the down position (2 wires). Set U Slider Tab, see Figure 10.
Wiring NOTES: 1 Available wiring configurations differ by product models/product numbers. 2 Use 18- to 22- gauge thermostat wire. Shielded cable is not required. 3 Set the R Slider Tab on the UWP to the up position (1 wire) for 1 transformer systems or the down position (2 wires) for 2 transformer systems. See "Setting Slider Tabs" on page 4. 4 Set the U Slider Tab to the up position (1 wire) for non-powered ventilation or the down position (2 wires) for powered ventilation.
Heat pumps systems 1H/1C Heat Pump System R Power Rc [R+Rc joined by Slider Tab] Y Compressor contactor C 24VAC common O/B Changeover valve G Fan relay 2H/2C Heat Pump System R Power Rc [R+Rc joined by Slider Tab] Y Compressor contactor (stage 1) C 24VAC common O/B Changeover valve G Fan relay Y2 Compressor contactor (stage 2) L Heat pump fault input 2H/1C Heat Pump System R Power Rc [R+Rc joined by Slider Tab] Y Compressor contactor C 24VAC common O/B Changeover valve G Fan relay Aux Auxiliary heat E Eme
Ventilation systems NOTE: Ventilation is not available on all models. Using U Slider Tab Wired to ERV/HRV whole house ventilator with internal power supply. Wired to fresh air damper powered by furnace transformer. 11 12 Mounting thermostat 1 Push excess wire back into the wall opening. 2 Close the UWP door. It should remain closed without bulging. 3 Align the UWP with the thermostat, and push gently until the thermostat snaps in place.
Installer setup – using the thermostat Setup using the thermostat • After the Lyric thermostat has powered up, touch START SETUP on the thermostat. You’ll be asked if you want to perform setup via Lyric app. Touch No. No • Touch or to toggle between Installer Set Up (ISU) options. • Touch Edit or touch text area, and then touch or to edit default setup option.
Installer setup – using the Lyric app Setup using the Lyric app Download the Lyric app from App Store or Google Play to use a hidden PRO installation feature that will allow you to configure the thermostat and personally invite your customer to connect to the installed thermostat at the same time. Lyric Enter Contractor Mode To enter Contractor Mode, press and hold the Lyric logo for 5 seconds. Then tap Confirm to begin using Contractor Mode.
Key features System status information Cool On, Heat On Emergency Heat On, Recovery, or Auto Changeover On. Schedule information Following time-based or location-based temperature control. Desired Temperature Displays the current desired temperature setting. Connection status information Status of Wi-Fi Connection: Connected, Disconnected, or Wi-Fi is Off. Time, ISU #, or Alert # AM Recovery Heat On Following Schedule Auto Chg.
Heat Stages/Aux/E Stages (#200=Conv./ 200=HP) Fan Control Aux/E Control Aux Heat Type 230 253 255 Equipment Type 205 221 System Type 200 Cool Stages (#200=Conv./ 200=HP) Outdoor Temp 130 220 Temp Scale 125 Reversing Valve Schedule Type 120 218 ISU Name # ISU Maximum of 2 Heat Stages for conventional systems. Maximum of 1 Aux/E stages for heat pump systems. This ISU is only displayed if ISU 205 is set to Electric Forced Air or Fan Coil.
ISU Name EM Heat Type Fossil Kit Control Auto Changeover Auto Differential High Cool Stage Finish High Heat Stage Finish Aux Heat Droop Up Stage Timer Aux Heat Balance Point (Compressor Lockout) # ISU 256 260 300 303 305 306 340 350 355 Notes This ISU is displayed only if ISU 200 is set to Heat Pump AND if ISU 221 Aux/E heat stages = 1 AND if ISU 253 is set to run AUX/E heat separately. Note: This ISU may not be available at all on some models.
ISU Name Aux Heat Lock Out (Aux Heat Outdoor Lockout) Cool 1 CPH (Cooling cycle rate stage 1) Cool 2 CPH (Cooling cycle rate stage 2) Heat 1 CPH (Heating cycle rate stage 1) Heat 2 CPH (Heating cycle rate stage 2) Aux Heat CPH (Heating cycle rate Auxiliary Heat) EM Heat CPH (Heating cycle rate Emergency Heat) Compressor Protection Ext Fan Run Time in Cool # ISU 356 365 366 370 371 375 378 387 390 This ISU is only displayed when Cool /Compressor Stages is set to 1 or more stages.
Temperature Control 520 Dehum Filter Reminder Sensor type 515 921 Indoor Sensor 500 Hum Pad Reminder Lock Screen 435 810 Min Heat Temperature 432 Air Filter 2 Reminder Max Heat Temperature 431 712 Min Cool Temperature 430 Air Filter 1 Reminder Max Cool Temperature 429 Air Filters Adaptive Recovery 425 711 Ext Fan Run Time in Heat 391 702 ISU Name # ISU After the call for heating ends, the thermostat keeps the fan on for the selected amount of time for increased efficiency.
High Outdoor Dewpoint Vent Lockout Vent Percent On Time 1011 1015 Vent Rate 1009 High Outdoor Temp Vent Lockout Home Size 1008 1014 Bedrooms 1007 Low Outdoor Temp Vent Lockout Vent Fan Control 1006 1013 Vent Method 1005 Vent Priority Vent Type 1000 1012 ISU Name # ISU Notes None: The thermostat does not control ventilation. ERV/HRV: The thermostat controls an Energy Recovery Ventilator or Heat Recovery Ventilator for ventilation.
ISU Name Vent Core Reminder Vent Filter Reminder UV Devices UV Bulb 1 Reminder UV Bulb 2 Reminder Idle Brightness Clock Format Daylight Saving Temp Offset # ISU 1017 1018 1100 1105 1106 1401 1410 1415 1420 Set to Off in areas that do not follow Daylight Saving Time. 0 °F - No difference in displayed temperature and the actual room temperature. The thermostat can display up to 3 °F (1.5 C) lower or higher than the actual measured temperature.
Performing a system test You can test the system setup in ADVANCED MENU under SYSTEM TEST option. 1 Press and hold Menu on the Lyric thermostat for 5 seconds to access ADVANCED MENU options. 2 Touch 3 Touch Select or touch text area. 4 Touch or to select system test type. Touch Select or touch text area. 5 For the heat test and cool test, use or to activate each stage of the equipment. For the fan test, use or to turn the fan on and off. or to go to SYSTEM TEST.
Troubleshooting Screen is blank • Check circuit breaker and reset if necessary. • Make sure power switch at heating and cooling system is on. • Make sure furnace door is closed securely. Screen is difficult to read • Change screen brightness in thermostat Menu. Increase brightness intensity for inactive backlight of the thermostat screen (max. is level 5). Heating or cooling system does not respond • Touch Mode to set system to Heat. Make sure the temperature is set higher than the Inside temperature.
Alerts and reminders Number Alert/Reminder Definition 181 Replace Air Filter (1) Replace air filter (1). Reset the timer by touching the "dismiss" button on thermostat screen after it is replaced. 182 Replace Air Filter (2) Replace air filter (2). Reset the timer by touching the "dismiss" button on thermostat screen after it is replaced. 183 Clean Humidifier Tank and Replace Water Filter Clean humidifier tank and replace the water filter, or contact dealer to do this for you.
CAUTION: ELECTRICAL HAZARD Can cause electrical shock or equipment damage. Disconnect power before beginning installation. CAUTION: EQUIPMENT DAMAGE HAZARD Compressor protection is bypassed during testing. To prevent equipment damage, avoid cycling the compressor quickly. CAUTION: MERCURY NOTICE If this product is replacing a control that contains mercury in a sealed tube, do not place the old control in the trash.