TH6220D1002 Installation Instructions

6
7 Auxiliary heat
cycle rate (CPH)*
Only TH6320U
for 3H/2C Heat
Pumps
5 For gas or oil furnaces of less than 90% efficiency
1 For steam or gravity systems
3 For hot water systems & furnaces of over 90% efficiency
9 For electric furnaces
9 Stage 1 compressor
cycle rate (CPH)
3 Recommended for most compressors
[Other cycle rate options: 1, 2, 4, 5 or 6 CPH]
10 Stage 2 compressor
cycle rate (CPH)
3 Recommended for most compressors
[Other cycle rate options: 1, 2, 4, 5 or 6 CPH]
12 Manual/Auto
changeover
0 Manual changeover (Heat/Cool/Off)
1 Auto changeover (Heat/Cool/Auto/Off)
2 Auto changeover only (Auto)
13 Adaptive Intelligent
Recovery™
1 On**See page 8
0 Off
14 Temperature
display
0 Fahrenheit
1 Celsius
15 Compressor
protection
5 Five-minute compressor off time
[Other options: 0, 1, 2, 3 or 4-minute off time]
16 Schedule format
0 5/2 (programmable weekdays and weekends)
1 5/1/1 (weekdays, Saturday & Sunday programmable)
27 Heat temperature
range stops
90 Max. heat temperature setting is 90 °F (32 °C)
[Other options: 40 °F to 89 °F (4.5 °C to 31.5 °C)]
28 Cool temperature
range stops
50 Min. cool temperature setting is 50 °F (10 °C)
[Other options: 51 °F to 99 °F (10.5 °C to 37 °C)]
Setup function Settings & options (factory default in bold)
Shaded areas below apply only to TH6320U/TH6220D or as otherwise noted.
Special function
Auto Changeover (Setup Function 12): When set to Auto, the thermostat automatically selects
heating or cooling depending on the indoor temperature. The thermostat will automatically adjust heat
and cool settings to maintain a 3-degree separation (fixed). Note: If you select Auto Changeover Only,
the System Setting on the thermostat will stay locked in the Auto position, preventing the user from
changing it to Em Heat, Heat, Cool or Off.
Adaptive Intelligent Recovery™ (Setup Function 13): Allows the thermostat to “learn
how long the furnace and air conditioner take to reach programmed temperature settings, so the
temperature is reached at the scheduled time.
Compressor Protection (Setup Function 15): Forces the compressor to wait a few minutes
before restarting, to prevent damage. During the wait time, the message Cool On or Heat On (heat
pumps only) will flash on the display.
*[Other cycle rate options: 2, 4, 6, 7, 8, 10, 11 or 12 CPH]