Thermostat User Manual

BACNET INTEGRATION MANUAL FOR TB7200 & TB7300 SERIES THERMOSTATS
63-4524—01 16
BACNET OBJECTS SUPPORTED
Device Objects
Table 4. Device Objects.
Object Name
Type and
Instance
Object Property Thermostat Parameter
TB7200X5x14B
TB73xxX5X14B
Device Object_Identifier
Property 75 (R,W)
Unique ID number of a device on a network.
Object_Name
Property 77 (R,W)
Unique name of a Device on a network.
Model Name
Property 70 (R)
Thermostat Model number.
Firmware Revision
Property 44 (R)
Current BACnet firmware revision used by the
thermostat.
Protocol Version
Property 98 (R)
Current BACnet firmware protocol version.
Default is Version 1.
Protocol Revision
Property 139 (R)
Current BACnet firmware protocol revision.
Default is Version 2.
Max ADPU Length
Property 62 (R)
Maximum ADPU Length accepted
Default is 244
ADPU Timeout
Property 10 (R)
ADPU timeout value
Default is 60,000 ms
Application-Software-
Version Property 12 (R)
Thermostat base application software version.
Default is based on current released version
Max_Master (R,W) Maximum master devices allowed to be part of the
network. 0 to 127, default is 127.
MS/TP_Address
Property 1001 (R,W)
BACnet MS-TP MAC Address. Proprietary attribute.
Default is as assigned by configuration.
MS/TP_Baud_Rate
Property 1002 (R,W)
BACnet MS-TP Baud-Rate. Proprietary attribute.
Range is: 1 = 9.6 KBps, 2 = 19.2 KBps, 3 = 38.4 KBps, 4
= 76.8 KBps and 5 = Auto Baud Rate. Index 5 is Write
only. Reading attribute will state current Baud rate used.
Writing index 1 to 4 will fix the Baud rate to the desired
value.