Thermostat User Manual

BACNET INTEGRATION MANUAL FOR TB7200 & TB7300 SERIES THERMOSTATS
11 63-4524—01
TB7300 Integration – Graphical User Interface (GUI) Objects
The following objects should be typically used in a GUI:
Room Temperature (AV7);
Occupied and Unoccupied Heat Setpoints (AV 39 and AV43);
Occupied and Unoccupied Cool Setpoints (AV 40 and AV34);
Room Humidity (AV10) (If available);
Room Humidity Setpoint (AV 71) (If available);
Outdoor Temperature (AV 9);
Supply Temperature (AI12) (If available);
Occupancy Command (MV18);
System Mode (MV16);
Fan Mode (MV17);
Fan Status (MV28);
Heating Valve Status (MV26);
Cooling Valve Status (MV28);
PI Heating Demand (AV21);
PI Cooling Demand (AV22);
Window Alarm (BI 35);
Filter Alarm (BI 36);
Service Alarm (BI 37)
Fig. 8. Example of graphical user interface objects.