Product Overview

7$%',*,7$/:$//02'8/(6
5 74-3097
6HW)DQ0RGH
The UNIT ENABLE button switches the fan mode between
AUTO and MANU OFF:
AUTO
(fan speed from controller)
MANU OFF
(fan off)
With this setting, depending
on configuration, the display
may also read:
+XPLGLW\'LVSOD\
If applicable, the humidity is indicated by the bargraph at the
top of the LCD. Each segment of the bargraph represents 4%
of relative humidity:
127( Humidity display is not available with fan control.
Humidity mode
(e.g., left 12 segments ON =
50% relative humidity)
6HW%\SDVV2FFXSDQF\0RGH'LVSOD\
The bypass function can be used to override the control
algorithm generated by the controller (e.g., for an event after
normal office hours, or for a room that is known not to be
used).
The status of the occupancy mode can be seen from the
sun-, moon-, and snowflake symbols. The following LCD
behaviors are possible, depending on configuration (see
T7560A,B Installation Instructions, form 95-7620 for
configuration options):
2FFXSDQF\PRGHGLVSOD\IRU([FHO/&'VLJQDOLQJ
([FHOVHWWR/&'B',63/$<ZLWK)&8+<'&+&RQO\
VHH7$%,QVWDOODWLRQ,QVWUXFWLRQVIRUP
Effective Occupancy or Bypass mode
(SUN continuously ON)
Effective Standby mode; generated by
time program
(HALF-SUN continuously ON)
Effective Unoccupancy mode
(MOON continuously ON)
Unit Off, No Frost Protection
(OFF without snowflake)
Unit Off, With Frost Protection
(OFF WITH SNOWFLAKE)
Override Standby mode (from central)
(HALF-SUN FLASHING)
Wink mode (network ID sent)
(SUN/MOON/SNOWFL. FLASHING)
(Only with FCU, HYD, CHC)
Press the BYPASS button to set the desired mode:
Press and release BYPASS button
to activate Override Occupancy or Bypass mode
Press and hold BYPASS button for at least 5 sec.
to activate Override Unoccupancy mode
Press and release BYPASS button again
to return to normal mode
127( Pressing the BYPASS button for more than 5
seconds sends the NEURON
©
ID of the connected
Excel 10 controller via the L
ONWORKS
©
network.
Override Occupancy or Bypass mode
(SUN FLASHING)
Override Unoccupancy mode
(MOON FLASHING)
2YHUULGHPRGHGLVSOD\IRU([FHO/('VLJQDOLQJ
([FHOVHWWR/('B29(55,'(
Off Conditions, No Override, Overr.
Occupancy, Overr. Standby (NO
SYMBOLS)
Wink mode (network ID sent)
(SUN/MOON/SNOWFL. FLASHING)
(Only with FCU, HYD, CHC)
Press the BYPASS button to set the desired mode:
Press and release BYPASS button
to activate Override Bypass mode
Press and hold BYPASS button for at least 5 sec.
to activate Override Unoccupancy mode
Press and release BYPASS button again
to return to normal mode
127( Pressing the BYPASS button for more than 5
seconds sends the NEURON
©
ID of the connected
Excel 10 controller via the L
ONWORKS
©
network.
Override Bypass mode
(SUN FLASHING)
Override Unoccupancy mode
(MOON FLASHING)
$872
0$18
0$18
0$18
0$18